10 Repair Coupling (B × B) ................. 10
11 Single-Tapped Coupling (B × B × AWWA) ...................... 11
12 Single-Tapped Coupling (B × B × NPT) ....
13 Double-Tapped Coupling (B × B × AWWA × AWWA).................... 12
14 Plug (Sp) ............ ...... 12
15 Tapped Plug (Sp × NPT)................. 13
16 IPS × CI Adapter (B × Sp) ............... 13
17 Cap (B) ................ .......... 14
18 Hydrant Tees............ ....... 14
19 Temperature Coefficients................. 16
20 Allowable Maximum Occasional Surge Pressure Capacity and Allowable Sudden Changes in Water Velocity for Pipe Operating at 73°F (23°C) at Working Pressures Expressed as Percent of Nominal Pressure Class (PC) . 16
This foreword is for information only and is not a part of ANSI*/AWWA C907.
I. Introduction.
I.A. Background. Injection-molded, gasketed PVC fittings are suitable for use exclusively with PVC pipe for underground pressure applications.
I.B. History. This is the third edition of ANSI/AWWA C907. In 1966, AWWA appointed Committee 8350-D to study and report on the adaptability of plastic pipe for use within the water industry. The committee presented its report on June 7, 1967, at AWWA’s annual conference. The report included a recommendation that a task group be appointed to prepare standards for the use of plastic materials. The AWWA Standards Committee on Thermoplastic Pressure Pipe was established in 1968. Following years of very productive work, the committee was dissolved in June 1988 and replaced by two committees on plastic products: one for polyolefin and one for polyvinyl chloride (PVC) products. The AWWA Committee on PVC Pressure Pipe and Fittings, which prepared this standard, was formed at that time. The first edition of ANSI/AWWA C907, Polyvinyl Chloride (PVC) Pressure Fittings for Water—4 in. Through 8 in. (100 mm Through 200 mm), was approved by the AWWA Board of Directors on June 23, 1991. The second edition, Injection-Molded Polyvinyl Chloride (PVC) Pressure Fittings, 4 In. Through 12 In. (100 mm Through 300 mm), for Water Distribution, was approved on June 13, 2004. This third edition was approved on June 11, 2017.
I.C. Acceptance. In May 1985, the US Environmental Protection Agency (USEPA) entered into a cooperative agreement with a consortium led by NSF International (NSF)† to develop voluntary third-party consensus standards and a certification program for direct and indirect drinking water additives. Other members of the original consortium included the Water Research Foundation (formerly AwwaRF) and the Conference of State Health and Environmental Managers (COSHEM). The American Water Works Association (AWWA) and the Association of State Drinking Water Administrators (ASDWA) joined later. In the United States, authority to regulate products for use in, or in contact with, drinking water rests with individual states.‡ Local agencies may choose to impose requirements more stringent than those required by the state. To evaluate the health
* American National Standards Institute, 25 West 43rd Street, Fourth Floor, New York, NY 10036.
†NSF International, 789 North Dixboro Road, Ann Arbor, MI 48105.
‡ Persons outside the United States should contact the appropriate authority having jurisdiction.
effects of products and drinking water additives from such products, state, provincial, and local agencies may use various references, including
1. Specific policies of the state, provincial, or local agency.
2. Two standards developed under the direction of NSF: NSF/ANSI 60, Drinking Water Treatment Chemicals—Health Effects, and NSF/ANSI 61, Drinking Water System Components—Health Effects.
3. Other references, including AWWA standards, Food Chemicals Codex, Water Chemicals Codex,* and other standards considered appropriate by the state, provincial, or local agency.
Various certification organizations may be involved in certifying products in accordance with NSF/ANSI 61. Individual states or local agencies have authority to accept or accredit certification organizations within their jurisdictions. Accreditation of certification organizations may vary from jurisdiction to jurisdiction. Annex A, “Toxicology Review and Evaluation Procedures,” to NSF/ANSI 61 does not stipulate a maximum allowable level (MAL) of a contaminant for substances not regulated by a USEPA final maximum contaminant level (MCL). The MALs of an unspecified list of “unregulated contaminants” are based on toxicity testing guidelines (noncarcinogens) and risk characterization methodology (carcinogens). Use of Annex A procedures may not always be identical, depending on the certifier.
ANSI/AWWA C907 does not address additives requirements. Users of this standard should consult the appropriate state, provincial, or local agency having jurisdiction in order to
1. Determine additives requirements, including applicable standards.
2. Determine the status of certifications by parties offering to certify products for contact with, or treatment of, drinking water.
3. Determine current information on product certification.
II. Special Issues.
II.A. Proper Design Consideration. Attention should be called to the need for users of this standard to provide proper design consideration for
1. Trench support.
2. Thrust restraint at areas of unbalanced forces.
3. Long-term effect of any anticipated cyclic transient surge pressures.
* Both publications available from National Academy of Sciences, 500 Fifth Street, NW, Washington, DC 20001.
4. Exact critical external or internal dimensions, which should be obtained from the manufacturer.
II.B. Gasket Materials.
II.B.1 Selection of Gasket Materials. The selection of materials is critical for water service and distribution piping in locations where there is a possibility that elastomers will be in contact with chlorine or chloramines. Document research has shown that elastomers such as gaskets, seals, valve seats, and encapsulations may degrade when exposed to chlorine or chloramines. The impact of degradation is a function of the type of elastomeric material, chemical concentration, contact surface area, elastomer cross section, and environmental conditions as well as temperature. Careful selection of and specifications for elastomeric materials and the specifics of their application for each water system component should be considered to provide long-term usefulness and minimum degradation (swelling, loss of elasticity, or softening) of the elastomer specified. II.B.2 Gasket Degradation Study. A pipe gasket, having the hardness of a compressed elastomer with a large mass relative to the small exposed surface area, thus experiences minimal degradation. This was validated in a research paper reported in Journal AWWA, Volume 96, Number 4, April 2004, pages 153–160, where the pipe gasket degradation in a 110 mg/L chloramine solution was found to degrade just the exposed surface.
III. Use of This Standard. It is the responsibility of the user of an AWWA standard to determine that the products described in that standard are suitable for use in the particular application being considered. Accordingly, each user of this standard is responsible for determining that the standard’s provisions are suitable for, and compatible with, that user’s intended application.
III.A. Purchaser Options and Alternatives. The following items should be provided by the purchaser.
1. Standard to be used—that is, ANSI/AWWA C907, Injection-Molded Polyvinyl Chloride (PVC) Pressure Fittings, 4 in. Through 12 in. (100 mm Through 300 mm), for Water, Wastewater, and Reclaimed Water Service, of latest revision.
2. Whether compliance with NSF/ANSI 61, Drinking Water System Components—Health Effects, is required.
3. Details of other federal, state or provincial, and local requirements (Sec. 4.2).
4. Fittings.
a. Nominal size, for example, 6 in. (150 mm); or, for tees, 6 in. × 6 in. × 4 in. (150 mm × 150 mm × 100 mm) where naming sequence is body size × body size × leg size.
b. Configuration (for example, tee).
c. Quantity of each size and configuration to be provided.
5. Request for change in testing temperature. (Sec. 5.1.1.1).
6. Requested selection of fittings for testing (Sec. 5.1.1.2).
7. Request for test records (Sec. 5.1.4.2).
8. Request for notification of time and date for in-plant inspection (Sec. 5.2).
9. Request for an affidavit of compliance (Sec. 6.3).
III.B. Modification to Standard. Any modification of the provisions, definitions, or terminology in this standard must be provided by the purchaser. IV. Major Revisions. Major changes made to the standard in this revision include the following:
1. 10-in. and 12-in. 90° bend were added to Table 7.
2. 6 × 6 and 8 × 6 hydrant tees were added to Table 18.
3. Added discussion of elastomers and chloramines to foreword.
V. Comments. If you have any comments or questions about this standard, please call AWWA Engineering and Technical Services at 303.794.7711, FAX at 303.795.7603; write to the department at 6666 West Quincy Avenue, Denver, CO 80235-3098; or email at standards@awwa.org.
SECTION 1: GENERAL
Sec. 1.1 Scope
This standard describes Pressure Class 235 (PC235) polyvinyl chloride (PVC) injection-molded fittings with push-on rubber-gasketed joints in nominal sizes 4 in. through 12 in. (100 mm through 300 mm)* for use in water, wastewater, and reclaimed water service. The fittings are for use with PVC and molecularly oriented polyvinyl chloride (PVCO) pressure pipe having an outside diameter conforming to the dimensions of cast-iron pipe and with dimension ratios (DRs) of 18 (Pressure Class 235) or 25 (Pressure Class 165), as described in ANSI/AWWA C900, Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 In. Through 60 In. (100 mm Through 1,500 mm), AWWA Manual M23—PVC Pipe—Design and Installation,
* Throughout the body of this standard, metric equivalents (rounded) are set in parentheses next to the US customary units.
and ANSI/AWWA C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 In. and Larger.
Sec. 1.2 Purpose
The purpose of this standard is to provide the minimum requirements for PVC injection-molded pressure fittings, 4 in. to 12 in. (100 mm to 300 mm), for underground PVC and PVCO pressure-pipe systems.
Sec. 1.3 Application
This standard can be referenced in specifications for purchasing and receiving injection-molded PVC pressure fittings, 4 in. (100 mm) and larger, for PVC and PVCO pressure-pipe systems. The stipulations of this standard apply when this document has been referenced and then only to injection-molded PVC pressure fittings, 4 in. to 12 in. (100 mm to 300 mm), for PVC and PVCO pressure-pipe systems.
SECTION 2: REFERENCES
This standard references the following documents. In their latest editions, they form a part of this standard to the extent specified within the standard. In any case of conflict, the requirements of this standard shall prevail. ANSI*/AWWA C800—Underground Service Line Valves and Fittings. ANSI/AWWA C900—Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 In. Through 60 In. (100 mm Through 1,500 mm).
ANSI/AWWA C909—Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 In. and Larger. ASME† B1.20.1—Pipe Threads, General Purpose (Inch).
ASTM‡ D638—Standard Test Method for Tensile Properties of Plastics.
ASTM D1598—Standard Test Method for Time-to-Failure of Plastic Pipe Under Constant Internal Pressure. ASTM D1599—Standard Test Method for Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings.
ASTM D1784—Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds.
* American National Standards Institute, 25 West 43rd Street, Fourth Floor, New York, NY 10036.
†ASME International, 3 Park Avenue, New York, NY 10016.
‡ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428.
ASTM D2122—Standard Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings. ASTM D2837—Standard Test Method for Obtaining Hydrostatic Design Basis for Thermoplastic Pipe Materials or Pressure Design Basis for Thermoplastic Pipe Products.
ASTM D3139—Standard Specification for Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals. ASTM F477—Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe.
ASTM F610/F610M—Standard Practice for Evaluating the Quality of Molded Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings by the Heat Reversion Technique. AWWA Manual M23—PVC Pipe—Design and Installation.
NSF/ANSI 61—Drinking Water System Components—Health Effects.
SECTION 3: DEFINITIONS
The following definitions shall apply in this standard:
1. Day: A day is defined as a 24-hour period.
2. Dimension ratio (DR): The ratio of outside diameter to wall thickness, which is the same for all pipe sizes of a specific DR series. (For pipe covered by ANSI/AWWA C900, the DR is determined by dividing the average outside diameter of the pipe by its minimum wall thickness and rounding off the quotient, when necessary, to the nearest whole number.)
3. Long-term pressure strength (LTPS): The long-term hydrostatic internalpressure strength, in pounds per square inch (psi) or kilopascals (kPa), of a specific configuration and size of injection-molded PVC fitting for water service at a specific maximum operating temperature. The LTPS is determined by hydrostatic tests and detailed evaluation procedures in accordance with ASTM D2837, with internal pressure substituted for hoop stress. The LTPS of fittings in this standard is 470 psi (3,240 kPa) at 73.4°F (23°C).
4. Manufacturer: The party that manufactures, fabricates, or produces materials or products.
5. Molecularly oriented polyvinyl chloride (PVCO) plastic pipe: PVCO pipe is PVC pipe that attains higher hoop strength by reorienting the molecules through controlled post-extrusion expansion of the pipe.
6. Occasional (emergency or transient) surge pressure (Pos) : Surge pressures caused by emergency operations, usually the result of malfunction (such as power failure, sudden valve closure, or system component failure).
7. Polyvinyl chloride (PVC): Thermoplastic compounds prepared by combining PVC resin with modifiers to attain desirable properties, stabilizers for property control, lubricants for processing, and pigments for coloring.
8. Potable water: Water that is safe and satisfactory for drinking and cooking.
9. Pressure class: The design capacity to resist working pressure up to a maximum sustained operating temperature of 73.4°F (23°C) (Sec. 4.4). The methods for determining pressure class are stated in Sec. 4.4.
10. Purchaser: The person, company, or organization that purchases any materials or work to be performed.
11. Reclaimed water: Wastewater that becomes suitable for beneficial use as a result of treatment.
12. Recurring (cyclic) surge pressure (PRS) : Surge pressures that occur frequently and are inherent to the design and operation of the system (such as normal pump startup or shutdown and normal valve opening or closure). Recurring surge pressure may occur up to millions of times in a piping system’s lifetime.
13. Safety factor: A number by which the long-term pressure strength (LTPS) of a fitting is divided to determine what proportion of the LTPS can be used to calculate the pressure class of the fitting.
14. Supplier: The party that supplies materials or services. A supplier may or may not be the manufacturer.
15. Surge pressure: The maximum hydraulic transient pressure increase (sometimes called water hammer) in excess of the operating pressure that is anticipated in the system as the result of sudden changes in velocity of the water column. For purposes of product selection and design, this document considers the following two types of surges:
a. Recurring (cyclic) surge pressure (PRS)
b. Occasional (emergency or transient) surge pressure (Pos)
Note: Occasional transients caused by emergency pump and valve operations are usually severe. The system should be designed to withstand positive and negative pressures caused by these emergency operations. Water column separation may occur if the negative pressure is reduced to the vapor pressure of the liquid. Rejoining of the separated water column typically results in a large pressure rise,
which will possibly damage the pipe system. Whenever possible, water column separation should be avoided.
16. Wastewater: A combination of the liquid and water-carried waste from residences, commercial buildings, industrial plants, and institutions, together with any groundwater, surface water, and stormwater that may be present.
17. Working pressure (WP): The maximum anticipated sustained operating pressure applied to the pipeline exclusive of transient pressures.
SECTION 4: REQUIREMENTS
Sec. 4.1 Permeation
The selection of materials is critical for distribution piping in locations where there is likelihood the pipe will be exposed to significant concentrations of pollutants composed of low-molecular-weight petroleum products or organic solvents or their vapors. Documented research has shown that pipe materials, such as polyethylene, and polyvinyl chloride and elastomers, such as those used in jointing gaskets and packing glands, are subject to permeation by low-molecular-weight organic solvents or petroleum products. If a potable water, wastewater, or reclaimed water pipe must pass through such a contaminated area or an area subject to contamination, consult with the manufacturer regarding permeation of pipe walls, jointing materials, and so on before selecting materials for use in that area.*
Sec. 4.2 Materials
4.2.1 Materials. Materials shall comply with the requirements of the Safe Drinking Water Act and other federal regulations for potable water systems. Therefore, it is the responsibility of the manufacturer and the purchaser to verify the current requirements of federal, state or provincial, and local regulations.
4.2.2 Fittings. Fittings shall be made from virgin PVC homopolymer compounds with a minimum cell class of 12454 capable of satisfying the longterm performance requirements of Sec. 5.1.2.2 and requirements for potable-water service (see foreword, Sec. I.C). The compound shall be classified in accordance with ASTM D1784.
* Guidance regarding the permeation resistance of pipe and pipe gasket materials is available in Impact of Hydrocarbons on PE/PVC Pipes and Pipe Gaskets, Denver CO: AwwaRF 2007.
4.2.3 Rework materials. Clean rework materials generated from the manufacturer’s own fitting production may be used by the same manufacturer for the same purposes provided that the finished products meet the requirements of this standard.
4.2.4 Certification for potable-water service. PVC compounds and products shall be tested for chemical extractants and certified as suitable for potable-water distribution service by an accredited testing agency acceptable to the purchaser in accordance with requirements that are no less restrictive than the applicable requirements specified in NSF/ANSI 61.
4.2.5 Gaskets and lubricants. Gaskets and lubricants intended for use with PVC fittings shall be made from materials that are compatible with the plastic material and with each other when used together and shall neither support the growth of bacteria nor adversely affect the quality of the water to be transported.
4.2.6 Elastomeric gaskets. One gasket shall be supplied for each bell of each fitting. Elastomeric gaskets shall be molded in one piece and shall conform to the requirements of ASTM F477 for high-head application.
Sec. 4.3 Fitting Requirements
4.3.1 Workmanship. Fittings shall be homogeneous throughout and shall be free from voids, cracks, and inclusions. The sealing surfaces of integral-bell sockets shall be free from nicks and scratches that might cause leakage at the joints. The plane of the face of the bells shall be at right angles to the centerline of the flow. The fittings shall be as uniform as commercially practical in color, density, and other physical properties.
4.3.2 Dimensions. The dimensions of the fittings presented in Figures 1 through 18 and Tables 1 through 18 are typical and meant as a guide only. The manufacturer shall provide to the purchaser, on request, all standard product dimensions and tolerances for the fitting, bell, and gasket (such as maximum allowable insertion depth and maximum allowable joint deflection). The following notes apply to Figures 1 through 18, Tables 1 through 18, and the full line of products contained in this standard:
a. B = gasketed bell end; Sp = pipe spigot end
b. AWWA = AWWA Thread ANSI/AWWA C800; NPT = National
Pipe Thread ASME B1.20.1
c. Not all fittings are available in all sizes
d. IPS = iron pipe size: CI = cast iron

| Nominal Pipe Size | Pressure Class at 73.4°F (23°C) | DR Maximum | Minimum Wall Thickness | Minimum Bell Inside Diameter | Minimum Inside Diameter | Minimum Bell Depth | |||||||||
| in. | (mm) | psi | (kPa) | Bell | Body | F1 in. | (mm) | F2 in. | (mm) | A, in. | (mm) | C, in. | (mm) | B, in. | (mm) |
| 4 | (100) | 235 | (1,620) | 18 | NA | 0.303 | (7.70) | 0.334 | (8.48) | 4.83 | (122.7) | 4.416 | (112.2) | 3.00 | (76.2) |
| 6 | (150) | 235 | (1,620) | 18 | NA | 0.434 | (11.02) | 0.479 | (12.17) | 6.93 | (176.0) | 6.348 | (161.2) | 3.50 | (88.9) |
| 8 | (200) | 235 | (1,620) | 18 | NA | 0.569 | (14.45) | 0.629 | (15.98) | 9.08 | (230.6) | 8.326 | (211.5) | 4.00 | (101.6) |
| 10 | (250) | 235 | (1,620) | 18 | NA | 0.701 | (17.81) | 0.770 | (19.56) | 11.19 | (284.2) | 9.870 | (250.7) | 4.50 | (114.3) |
| 12 | (300) | 235 | (1,620) | 18 | NA | 0.831 | (21.10) | 0.916 | (23.27) | 13.26 | (336.8) | 12.146 | (308.5) | 5.00 | (127.0) |

| Nominal Size | A | C | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | (100) | 14.5 | (368) | 10.5 | (267) |
| 6 × 4 | (150 ×100) | 17.5 | (445) | 13.0 | (330) |
| 6 | (150) | 19.5 | (495) | 14.5 | (368) |
| 8 × 4 | (200 × 100) | 19.0 | (483) | 15.5 | (394) |
| 8 × 6 | (200 × 150) | 21.0 | (534) | 16.5 | (419) |
| 8 | (200) | 23.0 | (584) | 17.5 | (445) |
| 10 × 4 | 250 × 100 | 26.6 | 675 | 17.6 | 448 |
| 10 × 6 | 250 × 150 | 26.6 | 675 | 18.5 | 470 |
| 10 × 8 | 250 × 200 | 26.6 | 675 | 19.2 | 487 |
| 10 | 250 | 26.6 | 675 | 20.2 | 512 |
| 12 × 4 | 300 × 100 | 29.9 | 760 | 19.6 | 498 |
| 12 × 6 | 300 × 150 | 29.9 | 760 | 20.6 | 524 |
| 12 × 8 | 300 × 200 | 29.9 | 760 | 21.3 | 541 |
| 12 × 10 | 300 × 250 | 29.9 | 760 | 22.2 | 565 |
| 12 | 300 | 29.9 | 760 | 23.0 | 585 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 0.6 | 15.2 | 10.5 | 267 |
| 6 | 150 | 0.8 | 20.3 | 12.0 | 305 |
| 8 | 200 | 0.9 | 22.9 | 13.5 | 343 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 1.3 | 33.0 | 11.5 | 292 |
| 6 | 150 | 1.8 | 45.7 | 14.0 | 356 |
| 8 | 200 | 2.2 | 45.9 | 16.8 | 427 |
| 10 | 250 | 2.6 | 67.0 | 21.0 | 533 |
| 12 | 300 | 3.1 | 80.0 | 24.4 | 620 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 0.8 | 20.3 | 11.0 | 279 |
| 6 | 150 | 1.1 | 27.9 | 13.0 | 330 |
| 8 | 200 | 1.3 | 33.0 | 15.0 | 381 |
| 10 | 250 | 1.8 | 46.3 | 19.3 | 489 |
| 12 | 300 | 2.0 | 51.0 | 21.4 | 544 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 1.3 | 33.0 | 11.5 | 292 |
| 6 | 150 | 1.8 | 45.7 | 14.0 | 356 |
| 8 | 200 | 2.2 | 45.9 | 16.8 | 427 |

| Nominal Size | A | ||
| in. | (mm) | in. | (mm) |
| 4 | 100 | 10.1 | 257 |
| 6 | 150 | 13.9 | 353 |
| 8 | 200 | 16.9 | 429 |
| 10 | 250 | 20.2 | 512 |
| 12 | 300 | 23.0 | 585 |

| Nominal Size | A | ||
| in. | (mm) | in. | (mm) |
| 4 | 100 | 6.3 | 160 |
| 6 | 150 | 8.3 | 211 |
| 8 | 200 | 11.0 | 280 |
| 10 | 250 | 14.3 | 363 |

| Nominal Size | A | D | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 × 6 | 100 × 150 | 9.4 | 239 | 6.9 | 175 |
| 6 × 8 | 150 × 200 | 10.5 | 267 | 9.1 | 231 |
| 8 × 10 | 200 × 250 | 7.3 | 185 | 11.2 | 284 |
| 10 × 12 | 250 × 300 | 10.1 | 257 | 13.3 | 338 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 6.3 | 160 | 8.2 | 225 |
| 6 | 150 | 8.3 | 218 | 10.0 | 255 |
| 8 | 200 | 11.0 | 279 | 11.3 | 290 |
| 10 | 250 | 14.3 | 363 | 18.1 | 460 |

| Nominal Size × Outlet | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 × (3/4, 1, or 2) | 100 × (19, 25, or 50) | 6.3 | 160 | 10.2 | 259 |
| 6 × (3/4, 1, or 2) | 150 × (19, 25, or 50) | 8.3 | 216 | 13.3 | 338 |
| 8 × (3/4, 1, or 2) | 200 × (19, 25, or 50) | 11.0 | 279 | 14.9 | 378 |

| Nominal Size × Outlet | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 × (3/4, 1, or 2) | 100 × (19, 25, 38, or 50) | 6.3 | 160 | 10.2 | 259 |
| 6 × (3/4, 1, or 2) | 150 × (19, 25, 38, or 50) | 8.3 | 216 | 13.3 | 338 |
| 8 × (3/4, 1, or 2) | 200 × (19, 25, 38, or 50) | 11.0 | 279 | 14.9 | 378 |

| Nominal Size × C × E | A | B | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 6 × (3/4, 1, 11/4, 11/2, or 2) | 150 × (19, 25, 32, 38, or 50) | 14.4 | 366 | 8.7 | 221 |
| 8 × (3/4, 1, 11/4, 11/2, or 2) | 200 × (19, 25, 32, 38, or 50) | 15.0 | 381 | 11.3 | 287 |

| Nominal Size | A | C | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 4.5 | 114 | 4.8 | 122 |
| 6 | 150 | 6.4 | 163 | 6.9 | 175 |
| 8 | 200 | 7.3 | 185 | 9.1 | 231 |
| 10 | 250 | 9.0 | 229 | 11.1 | 282 |
| 12 | 300 | 9.8 | 249 | 13.2 | 335 |

| Nominal Size × C × E | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 × (3/4, 1, 11/2, or 2) | 100 × (19, 25, 38, or 50) | 4.8 | 122 | 4.5 | 114 |
| 6 × (3/4, 1, 11/2, or 2) | 150 × (19, 25, 38, or 50) | 6.9 | 175 | 6.4 | 163 |
| 8 × (3/4, 1, 11/2, or 2) | 200 × (19, 25, 38, or 50) | 9.1 | 231 | 7.3 | 185 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 2.7 | 69 | 7.0 | 178 |
| 6 | 150 | 3.7 | 94 | 8.6 | 218 |

| Nominal Size | A | L | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 4 | 100 | 6.3 | 160 | 4.5 | 115 |
| 6 | 150 | 8.0 | 205 | 5.0 | 125 |
| 8 | 200 | 11.0 | 280 | 6.0 | 150 |

| Nominal Size | A | C | |||
| in. | (mm) | in. | (mm) | in. | (mm) |
| 6 × 6 | 150 × 150 | 17.3 | 440 | 15.7 | 400 |
| 8 × 6 | 200 × 150 | 19.7 | 500 | 18.1 | 460 |
| 10 × 6 | 250 × 150 | 26.6 | 675 | 21.0 | 533 |
| 12 × 6 | 300 × 150 | 29.9 | 760 | 23.2 | 590 |
4.3.2.1 Ratio of outside diameter. The ratio of the measured outside diameter of the bell at any point (including the gasket groove) to the wall thickness at the same point must not exceed 18.
4.3.2.2 Minimum wall thickness. Minimum wall thickness of body of fitting is 125 percent of the wall thickness of Pressure Class 235 pipe (DR 18).
4.3.3 Fitting qualification test. Each molded fitting configuration and size shall be qualified by testing in accordance with Sec. 5.1.2.2. Representative fittings shall demonstrate an average extrapolated LTPS of 470 psi (3,240 kPa) at 100,000 hours.
4.3.4 Gasketed joints (bells). The gasketed joints of the fittings shall comply with the laboratory qualifying tests in ASTM D3139 using Pressure Class 235 (DR 18) PVC pipe with cast-iron (CI) outside diameter (ANSI/AWWA C900) to form the test assembly. The minimum short-term rupture pressure shall be 755 psi (5,210 kPa). This is a qualifying test for the joint design.
4.3.5 Quality control of fittings
4.3.5.1 Accelerated-regression test. Fittings shall be tested in accordance with Sec. 5.1.2.3. Representative fittings shall demonstrate a minimum extrapolated LTPS of 470 psi (3,240 kPa) at 100,000 hours.
4.3.5.2 Burst pressure. Test specimens shall not fail when raised to a pressure of 755 psi (5,210 kPa) in accordance with Sec. 5.1.2.4.
4.3.5.3 Heat-reversion test. Fittings shall be tested in accordance with Sec. 5.1.2.5. The estimation of quality shall be based on the suggested interpretation of results given in ASTM F610/F610M, appendix X1.
Sec. 4.4 Pressure Class of Fittings
The pressure class for injection-molded PVC fittings conforming to this standard is Pressure Class 235. The pressure class is determined using a safety factor (SF) of 2.0. The pressure class is determined from the following relationship:
PC = LTPS / SF (1)
Where:
PC = pressureclass(PressureClass235)
LTPS = long - term pressure strength is 470 psi (3,240 kPa)
SF = safetyfactoris2.0
Sec. 4.5 Pressure Class Thermal Derating Factors
If PVC Pressure Class 235 fittings are part of a pipeline that is used to convey fluids at sustained temperatures above 73.4°F (23°C) or if they are installed in an
| Sustained Service Temperature | Pressure Class Reduction Coefficient | |
| °F | (°C) | |
| 73.4 | (23) | 1.00 |
| 80.0 | (27) | 0.88 |
| 90.0 | (32) | 0.75 |
| 100.0 | (38) | 0.62 |
| 110.0 | (43) | 0.50 |
| 120.0 | (49) | 0.40 |
| 130.0 | (54) | 0.30 |
| 140.0 | (60) | 0.22 |
| DR | Pressure Class (PC) (psi) | Occasional Surge Pressure Capacity (psi) | Corresponding Sudden Delta V With WP = % of PC | |||
| 100% | 80% | 60% | 40% | |||
| (ft/sec) | (ft/sec) | (ft/sec) | (ft/sec) | |||
| 25 | 165 | 264 | 6.7 | 9.0 | 11.2 | 13.5 |
| 18 | 235 | 376 | 8.1 | 10.8 | 13.5 | 16.2 |
environment where sustained elevated temperatures can influence the conduit and fittings, the pressure class of the fittings must be multiplied by the appropriate reduction coefficient, as shown in Table 19.
Sec. 4.6 Surge Pressure
A detailed description of occasional and recurring surge pressures is included in ANSI/AWWA C900.
4.6.1 Occasional surge pressures. For fittings in pressure systems, the design requirements for occasional surges are the same as those required in ANSI/ AWWA C900 for PVC pipe (see Table 20). Occasional surges shall not exceed the short-term rating (STR) for DR18 PC235 pipe, which is 376 psi.
4.6.2 Recurring surge pressures. For fittings in pressure systems, the design requirements for recurring surges are not the same as for pipe. For some
applications not within the boundary of a looped water distribution system, such as a water transmission line, there is potential for large recurring surges. In these instances, the service life of the fitting may be less than the life of the pipe. Variations in fitting configurations, manufacturing processes, and service life adjustments require that the manufacturer be consulted for proper guidance. See Section 3 for definitions of recurring and occasional surge pressures.
SECTION 5: VERIFICATION
Sec. 5.1 Test Methods
5.1.1 Test preparation.
5.1.1.1 Conditioning. Tests shall be performed at 73.4°F ±3.6°F (23°C ±2°C) unless otherwise required in the contract documents. Fittings shall be conditioned at test temperatures in a liquid bath for a minimum of 1 hour or in a gaseous medium for a minimum of 16 hours before pressurizing.
5.1.1.2 Specimens. If not stipulated in this standard, selection of fittings for testing shall be as agreed on by the purchaser and the manufacturer.
5.1.2 Test methods.
5.1.2.1 Dimensions. All measurements shall be made in accordance with ASTM D2122.
5.1.2.2 Fitting qualification test. Each molded fitting configuration and size shall be qualified by subjecting representative specimens to long-term pressure tests as described in ASTM D1598, except as modified within this standard. Internal pressure is substituted for hoop stress. Pressure versus time-to-failure data, consisting of at least 10 data points and extending to at least 2,000 hours, shall be obtained in representative fitting specimens with end closures described in ASTM D1599, but otherwise in accordance with ASTM D1598. These data shall be used to develop an estimate of the fitting’s average 100,000-hour strength (expressed as internal pressure in psi or kPa) in accordance with the extrapolation method given in ASTM D2837. The data shall be entered as log pressure-to-failure (psi or kPa) versus log time-to-failure (hr), rather than the usual log stress-to-failure versus log time-to-failure. The data shall be considered unsuitable for extrapolation if the lower confidence limit at 100,000 hours is less than 85 percent of the estimated average pressure strength for the same time intercept.
5.1.2.3 Accelerated regression test. A minimum of six specimens of a single size and configuration of fitting shall be subjected to short-term pressure tests with end closures described in ASTM D1599 but otherwise in accordance with ASTM D1598. The fittings shall be tested at internal pressures calculated to cause failure (to yield data points) at the following time intervals:
a. 0.167 to 0.500 hours (10 minutes to 30 minutes)
b. 0.501 to 2.000 hours (30 minutes to 2 hours)
c. 2.001 to 15.000 hours
d. 15.001 to 100.000 hours
e. 100.001 to 100 + hours
f. 0 to 100 + hours (random point)
Additional points may be added to improve the precision of the extrapolation or to narrow the bandwidth of the confidence limits. No points shall be excluded unless an obvious defect is detected in the failure area of the test specimen. These data shall be used to develop an estimate of the fitting’s average 100,000-hour strength (expressed as internal pressure in psi or kPa) in accordance with the extrapolation method given in ASTM D2837.
5.1.2.4 Burst pressure. The ability of the fittings to withstand the quickburst pressure shall be determined by raising their internal pressure to the required minimum within 60 to 70 seconds in accordance with procedures given for fittings in ASTM D1599.
5.1.2.5 Heat-reversion test. Fittings shall be subjected to the heat-reversion test method given in ASTM F610/F610M.
5.1.3 Test frequency.
5.1.3.1 Dimensions. The dimensions of fittings produced from each mold cavity shall be measured at the beginning of production. Thereafter, one fitting from each mold cavity shall be measured after production of the both 80th fitting or on the last fitting of the production run if fewer than 80 fittings are produced. Any change to the injection parameters or material shall be interpreted as a new beginning of production.
5.1.3.2 Fitting qualification.
5.1.3.2.1 Each molded configuration and each size must meet the requirements of Sec. 4.3.3. Having met the requirements of Sec. 4.3.3, the qualified fitting may be produced without additional qualification tests, subject to the other requirements of this standard.
5.1.3.2.2 If the dimensions of a qualified fitting are changed, the fitting shall be retested in accordance with Sec. 5.1.2.2 to prove that it meets the requirements of Sec. 4.3.3.
5.1.3.2.3 If a change is made in the formulation of the PVC compound from which the fittings are manufactured or if a change is made in the supplier of the compound and if, in either case, the change is claimed by the manufacturer to have no effect on fitting quality, the following requalification test must be performed. Specimens of the largest size fitting made with the substituted compound shall be selected at random and tested in accordance with Sec. 5.1.2.2. The substituted compound shall be judged to be identical to the original compound provided the leastsquares regression line for the substituted compound obtained with test data for at least 15 data points, including at least one point beyond 2,000 hours, produces (1) a 100,000-hour LTPS of at least 470 psi (3,240 kPa) and (2) a 50-year LTPS that is not less than 85 percent of the 50-year LTPS of the original compound (to ensure that the slope for the substituted compound is approximately the same as that for the original compound). The test results shall be retained per Sec. 5.1.4.1.
5.1.3.3 Accelerated regression test. At the beginning of production and semiannually thereafter, specimens of nominal 4-in. (100-mm), 6-in. (150-mm), 8-in. (200-mm), 10-in. (250-mm), and 12-in. (300-mm) fittings that are made from each PVC fitting compound shall be tested in accordance with Sec. 5.1.2.3.
Note: These tests are meant to ensure continued qualification of the fittings and the injection molding process. This test is not intended to be performed for every production run for every configuration of every size.
5.1.3.4 Gasketed joints. The gasketed joints of the fittings shall be tested once by the manufacturer in accordance with Sec. 4.3.4 to qualify the joints for service and thereafter whenever the design of the joint or the gasket is changed.
5.1.3.5 Burst pressure. Testing shall be performed in accordance with Sec. 4.3.5.2. At least one fitting shall be selected at random from the beginning of a production run and shall be tested. During the production run of any one configuration and size of fitting, additional burst-pressure tests shall be performed at least once every 5 days. Use of a different PVC compound shall constitute the start of a new production run.
5.1.3.6 Heat-reversion test. One fitting shall be selected at random from each production run, no matter what size run of each configuration and size, and tested in accordance with Sec. 4.3.5.3.
5.1.3.7 Provision for test sample failure. Any fitting, plus the fittings represented by that fitting, shall be rejected if it does not meet one or more of the requirements in Sec. 4.3.5 of this standard. A quantity of specimens shall be subjected to the failed test method in numbers sufficient to determine which are acceptable of those produced from the same mold as of the last favorable test.
5.1.4 Retention of test results.
5.1.4.1 Qualification test. The manufacturer shall retain a permanent record of all tests performed in accordance with Sec. 4.3.3 of this standard.
5.1.4.2 Quality-control records. The manufacturer shall maintain, for a period of not less than 2 years, a record of quality-control tests and shall, if requested, submit the pertinent record to the purchaser.
Sec. 5.2 Inspection
5.2.1 General. Inspection by the purchaser shall not relieve the manufacturer of the responsibility for providing products that conform to the requirements set forth in this standard.
5.2.2 Notification to the purchaser. If an in-plant inspection of the product is specified by the purchaser, the manufacturer shall provide the purchaser advance notice of the date, time, and place of fitting testing so that the purchaser may be present.
5.2.3 Plant access. The purchaser’s inspector shall have free access at reasonable times to those parts of a manufacturer’s plant that are necessary to ensure that products comply with all requirements.
SECTION 6: DELIVERY
Sec. 6.1 Marking
6.1.1 General. Fittings shall bear identification markings that will remain legible during normal handling, storage, and installation, and that have been applied in a manner that will not reduce the strength of any product covered by this standard.
6.1.2 Required marking. Marking on the fitting shall include the following:
a. Nominal size and deflection angle if applicable (for example, 6-in.
45° bend, 8-in. tee, or 6-in. × 4-in. reducer).
b. PVC.
c. AWWA identification number for this standard (ANSI/AWWA C907).
d. Pressure class (PC235).
e. Manufacturer’s name or trademark and production record code.
f. Seal (mark) of the testing agency that verified the suitability of the fitting for potable water service (Sec. 4.2.3).
g. Maximum allowable joint deflection for each rubber gasket joint. (for example, “0-DEGREES DEFLECTION PER JOINT”)
Sec. 6.2 Shipping and Delivery
Fittings shall be packaged in crates or boxes to minimize possible excessive impacts, scratches, or gouges during transit. Scratches to a maximum depth of 10 percent of the fitting wall shall be permitted. Although fittings are lightweight, they should not be tossed or thrown during unloading or lowering into the trench for reasons of safety and to preserve structural integrity.
Sec. 6.3 Affidavit of Compliance
The purchaser may require an affidavit from the manufacturer or supplier that the material provided complies with applicable requirements of this standard.
Dedicated to the world’s most important resource, AWWA sets the standard for water knowledge, management, and informed public policy. AWWA members provide solutions to improve public health, protect the environment, strengthen the economy, and enhance our quality of life.