ANSI AWWA C909-16 Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 In.(100 mm) and La

文档天下 国外标准评论1阅读模式

1 General

1.1 Scope ........... ..... 1

1.2 Purpose ............ ...... 1

1.3 Application.......... ..... 2

2 References ...........

3 Definitions
......... ..... 3

4 Requirements

4.1 Permeation .......... ..... 6
4.2 Materials ......... ... 6
4.3 Pipe Requirements ............................ 7
4.4 Joint Requirements.......................... 11
4.5 Pressure-Class Designations ............ 11

SEC. PAGE

5 Verification

5.1 Quality-Control and Qualification Test Requirements ..................... 13
5.2 Quality-Control Records................. 15
5.3 Plant Inspection ............. ....... 15

6 Delivery

6.1 Marking ............. ....... 16
6.2 Shipping and Delivery..................... 16
6.3 Affidavit of Compliance .................. 17
6.4 Notice of Nonconformance ............. 17

Appendix

A Bibliography ............ ...... 19

Tables

1 Dimensions and Pressure Classes For PVCO Pressure Pipe With Ductile-Iron-Pipe-Equivalent ODs ..
2 Pressure-Test Requirements ............ 10
3 Temperature Coefficients, F T .......... 10
4 Allowable Maximum Occasional Surge Pressure Capacity and Allowable Sudden Changes in Water Velocity for Pipe Operating at 73°F (23°C) at Working Pressures Expressed as Percent of Nominal PC ............. 13
5 Time to Failure for Individual Data Points (Accelerated Regression Test) . 14

This page intentionally blank.

This foreword is for information only and is not a part of ANSI*/AWWA C909.

I. Introduction.

I.A. Background. Molecularly oriented polyvinyl chloride (PVCO) pressure pipe has been installed in Europe since the early 1970s, and in North America since 1991. The longitudinal molecular structure of polyvinyl chloride (PVC) is reoriented to a circumferential direction using heat and pressure. The manufacturing process begins by conventionally extruding a starting stock pipe. This starting stock piece is roughly half the diameter and twice the wall thickness of the finished PVCO pipe (e.g., starting stock with a nominal 3-in. [75-mm]† diameter and a 0.40-in. [10.2-mm] wall thickness becomes a finished PVCO pipe with a nominal 6-in. [150-mm] diameter and a 0.20-in. [5.1-mm] wall thickness). The starting stock piece is heated and then circumferentially expanded to its final dimensions. By circumferentially expanding the starting stock piece, a new molecular orientation is achieved. This new orientation increases physical and mechanical properties of the pipe. Tensile strength, and hence the hydrostatic design basis (HDB), is substantially increased from 4,000 psi to 7,100 psi (27.6 MPa to 49.0 MPa). This standard pertains to 4-in. (100-mm) and larger PVCO pressure pipe made from class 12454 material. The PVCO pressure pipe is designed to provide an HDB of 7,100 psi with ductile-iron-pipe-equivalent (DI) outside diameter (OD) dimensions. Previous editions have referenced cast-iron-pipe-equivalent (CI) outside diameters. DIOD and CIOD are one and the same (equal). The reference to DIOD is to maintain consistency with other AWWA standards. The wall thicknesses are sufficient to provide pressure classes 165 psi, 235 psi, and 305 psi while maintaining a long-term safety factor of 2.0.

Design considerations are provided in AWWA Manual M23, PVC Pipe—Design and Installation, which provides detailed information on PVCO pipe covered by ANSI/ AWWA C909. Recommended installation guidance is provided in ANSI/AWWA C605. Additional information may be found in ANSI/AWWA C110, C153, C900, C905, and C907 for use with the PVCO pipes covered by ANSI/AWWA C909. Fabricated PVC fittings for use with ANSI/AWWA C909 are included in ANSI/AWWA C900

* American National Standards Institute, 25 West 43rd Street, Fourth Floor, New York, NY 10036. † Metric conversions given in this standard are direct conversions of US customary units and are not those specified in International Organization for Standardization (ISO) standards.

and C905. Ductile-iron mechanical-joint fittings for use with ANSI/AWWA C909 are covered by ANSI/AWWA C110 and C153.

I.B. History. This is the fourth edition of ANSI/AWWA C909. In 1994, the PVC Pipe and Fittings Committee appointed a subcommittee to develop a standard for PVCO pressure pipe. The first edition of ANSI/AWWA C909 was approved by the AWWA Board of Directors in 1998. Subsequent editions were approved in 2002 and 2009. This edition was approved on Jan. 16, 2016.

I.C. Acceptance. In May 1985, the US Environmental Protection Agency (USEPA) entered into a cooperative agreement with a consortium led by NSF International (NSF) to develop voluntary third-party consensus standards and a certification program for direct and indirect drinking water additives. Other members of the original consortium included the Water Research Foundation (formerly AwwaRF) and the Conference of State Health and Environmental Managers (COSHEM). The American Water Works Association (AWWA) and the Association of State Drinking Water Administrators (ASDWA) joined later.

In the United States, authority to regulate products for use in, or in contact with, drinking water rests with individual states.* Local agencies may choose to impose requirements more stringent than those required by the state. To evaluate the health effects of products and drinking water additives from such products, state and local agencies may use various references, including

1. An advisory program formerly administered by USEPA, Office of Drinking Water, discontinued on Apr. 7, 1990.
2. Specific policies of the state or local agency.
3. Two standards developed under the direction of NSF†: NSF/ANSI‡ 60, Drinking Water Treatment Chemicals—Health Effects, and NSF/ANSI 61, Drinking Water System Components—Health Effects.
4. Other references, including AWWA standards, Food Chemicals Codex, Water Chemicals Codex,§ and other standards considered appropriate by the state or local agency.

Various certification organizations may be involved in certifying products in accordance with NSF/ANSI 61. Individual states or local agencies have authority to accept

* Persons outside the United States should contact the appropriate authority having jurisdiction.

†NSF International, 789 North Dixboro Road, Ann Arbor, MI 48105.

‡American National Standards Institute, 25 West 43rd Street, Fourth Floor, New York, NY 10036.

§Both publications available from National Academy of Sciences, 500 Fifth Street, NW, Washington, DC 20001.

or accredit certification organizations within their jurisdictions. Accreditation of certification organizations may vary from jurisdiction to jurisdiction. Annex A, “Toxicology Review and Evaluation Procedures,” to NSF/ANSI 61 does not stipulate a maximum allowable level (MAL) of a contaminant for substances not regulated by a USEPA final maximum contaminant level (MCL). The MALs of an unspecified list of “unregulated contaminants” are based on toxicity testing guidelines (noncarcinogens) and risk characterization methodology (carcinogens). Use of Annex A procedures may not always be identical, depending on the certifier.

ANSI/AWWA C909 does not address additives requirements. Thus, users of this standard should consult the appropriate state or local agency having jurisdiction in order to

1. Determine additives requirements, including applicable standards.
2. Determine the status of certifications by parties offering to certify products for contact with, or treatment of, drinking water.
3. Determine current information on product certification.

II. Special Issues. The material presented in this standard will be addressed in the third edition of AWWA Manual M23, which is currently in revision. The material published here ensures that users of this standard will have continuous access to the most up-to-date design information. The second edition of AWWA Manual M23 published in 2002 and this standard will not be compatible until the third edition of AWWA Manual M23 is revised and published. Where M23 (2002) does not match, the intent of this standard takes precedence, and design matters in the second edition of AWWA M23 that are inconsistent with this standard should be discussed with the manufacturer. II.A. Pipe Selection. II.A.1. Selection of Pressure Class. The minimum pressure class of the pipe selected should be equal to or greater than the system working pressure. The sum of the system working pressure and occasional surge pressure should not exceed 1.60 times the pressure class of the pipe. If surge pressures are severe, consideration should be given to removal of the cause of surge pressures or to the incorporation of surge suppressors in the system.

II.B. Gasket Materials.

II.B.1. Selection of Gasket Materials. The selection of materials is critical for water service and distribution piping in locations where there is a possibility that elastomers will be in contact with chlorine or chloramines. Documented research by Water Research Foundation (formerly American Water Works Association Research Foundation [AwwaRF]) has shown that elastomers such as gaskets, seals, valve seats, and

encapsulations may be degraded when exposed to chlorine or chloramines. The impact of degradation is a function of the type of elastomeric material, chemical concentration, contact surface area, elastomer cross section, and environmental conditions as well as temperature. Careful selection of and specifications for elastomeric materials and the specifics of their application for each water system component should be considered to provide long-term usefulness and minimum degradation (swelling, loss of elasticity, or softening) of the elastomer specified.

II.B.2. Minimal Degradation. A pipe gasket having the compressed hardness of an elastomer with a large mass relative to the exposed surface area experiences minimal degradation. This was validated in a research paper reported in Journal AWWA,* where the pipe gasket degradation in a 110-mg/L chloramine solution was found to be negligible.
III. Use of This Standard. It is the responsibility of the user of an AWWA standard to determine that the products described in that standard are suitable for use in the particular application being considered. Although this standard generally presents adequate information to order pipe to meet working pressure requirements, it does not include information to guide the designer in determining wall thicknesses, pipe flexibility requirements, and installation conditions to meet external loading conditions. Pipe designers should refer to AWWA Manual M23, PVC Pipe—Design and Installation (third edition forthcoming). In addition, consultation with pipe manufacturers is recommended.
III.A. Purchaser Options and Alternatives. The following items should be provided by the purchaser:

1. Standard used—that is, ANSI/AWWA C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 In. (100 mm) and Larger, of latest revision.
2. Details of other federal, state or provincial, and local requirements (Sec. 4.2.1).
3. Whether compliance with NSF/ANSI 61, Drinking Water System Components—Health Effects, is required (Sec. 4.2.4).
4. Pipe details.

a. Nominal size (for example, 4 in. [100 mm]).

b. Pressure class (see Table 1).

c. Linear feet of each pressure class for each nominal pipe size to be provided.

d. Whether drawings and calculations shall be provided by the manufacturer.

* Volume 96, Number 4, April 2004, pp. 153–160.

5. Standard lengths (Sec. 4.3.3.3).
6. Plant inspection. If plant inspections are desired, provisions must be specified in the purchase documents (Sec. 5.3).
a. Production notice. The manufacturer should be required to give adequate advance notice of when and where production of ordered materials will start.
b. Inspection aids. The manufacturer should be required to make available, without charge, to the purchaser’s inspector, the tools and assistance that are necessary for inspection and handling of materials.
c. Inspection limitations. To exclude inspection of proprietary manufacturing processes, the manufacturer should be required to give advance notice to the purchaser.

7. Shipping and delivery (Sec. 6.2).
8. Affidavit of compliance requirements (Sec. 6.3).

III.B. Modification to Standard. Any modifications to the provisions, definitions, or terminology in this standard must be provided by the purchaser. IV. Major Revisions. The major revisions to this edition include the following:

1. Increased scope from 4 in. to 24 in. to 4 in. and larger (Sec. 1.1).
2. Exchanged design factor with safety factor in equation used to calculate pressure class (Sec. 4.5.1).
3. Pipe burst strength test frequency increased for nominal pipe sizes greater than 12 in. (Sec. 5.1.4).

V. Comments. If you have any comments or questions about this standard, please contact AWWA Engineering and Technical Services at 303.794.7711, FAX at 303.795.7603; write to the department at 6666 West Quincy Avenue, Denver, CO 80235-3098; or email at standards@awwa.org.

This page intentionally blank.

SECTION 1: GENERAL

Sec. 1.1 Scope

This standard pertains to molecularly oriented polyvinyl chloride (PVCO) pressure pipe that is manufactured from starting stock pipe made from ASTM D1784 cell class 12454 material. The starting stock materials are then oriented through circumferential expansion to provide a hydrostatic design basis (HDB) of 7,100 psi (49.0 MPa). The pipe is primarily intended for use in transporting potable water, wastewater, and reclaimed water in buried installations. Pipe outside diameters (ODs) conform to those established for ductile-iron (DI)-equivalent ODs (DIODs). Pressure classes range from 165 psi to 305 psi (1,140 kPa to 2,100 kPa) in sizes 4 in. (100 mm) and larger.

Sec. 1.2 Purpose

The purpose of this standard is to provide purchasers, manufacturers, and suppliers with the minimum requirements for PVCO pressure pipe, 4 in. (100 mm) and larger, for potable water, wastewater, and reclaimed water service.

Sec. 1.3 Application

This standard can be referenced in documents for purchasing and receiving PVCO pressure pipe, 4 in. (100 mm) and larger, for potable water, wastewater, and reclaimed water service. The stipulations of this standard apply when this document has been referenced and then only to PVCO pressure pipe, 4 in. (100 mm) and larger, for potable water, wastewater, and reclaimed water service.

SECTION 2: REFERENCES

This standard references the following documents. In their latest editions, they form a part of this standard to the extent specified within the standard. In any case of conflict, the requirements of this standard shall prevail. ASTM* D1598-15a—Standard Test Method for Time-to-Failure of Plastic Pipe Under Constant Internal Pressure.

ASTM D1599-14e1—Standard Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings. ASTM D1784-11—Standard Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds.

ASTM D2122-15—Standard Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings. ASTM D2152-13—Standard Test Method for Adequacy of Fusion of Extruded Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by Acetone Immersion.

ASTM D2241-15—Standard Specification for Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series). ASTM D2290-12—Standard Test Method for Apparent Hoop Tensile Strength of Plastic or Reinforced Plastic Pipe.

ASTM D2412-11—Standard Test Method for Determination of External Loading Characteristics of Plastic Pipe by Parallel-Plate Loading. ASTM D2837-13e1—Standard Test Method for Obtaining Hydrostatic Design Basis for Thermoplastic Pipe Materials or Pressure Design Basis for Thermoplastic Pipe Products.

ASTM D3139-98—Standard Specification for Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals. ASTM F477-14—Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe. NSF*/ANSI† 61—Drinking Water System Components—Health Effects. PPI‡ TR-3—Policies and Procedures for Developing Recommended Hydrostatic Design Basis (HDB), Hydrostatic Design Stresses (HDS), Pressure Design Basis (PDB), Strength Design Basis (SDB), Minimum Required Strength (MRS) Ratings, and Categorized Required Strength (CRS) for Thermoplastic Piping Materials or Pipe.

SECTION 3: DEFINITIONS

The following definitions shall apply in this standard:

1. Constructor: The party that provides the work and materials for placement or installation.
2. Design factor (DF): The inverse of the safety factor. It is used to reduce the hydrostatic design basis (HDB) to arrive at the hydrostatic design stress (HDS) from which the pressure class (PC) is calculated. Unless otherwise noted, the design factor used in this standard is 0.5.

Note: Because the effective strength of PVCO materials depends on the temperature and on the duration of stress application, the effective safety factor when using a DF of 0.5 will vary with end-use conditions. For the PVC material described in this standard, the effective safety factor against sustained pressures is at least 2.0. The actual value is generally larger and depends on the magnitude of the applied transient and sustained pressures as well as on the operating temperature.

3. Expansion ratio (ER): The ratio of the outside diameter of the finished PVCO pipe to the outside diameter of the original starting stock.

4. Hydraulic transients: Hydraulic transients (sometimes called water hammer) are pressure fluctuations caused by changes in the velocity of the water column resulting from such actions as operating a valve or a pump. The pressure fluctuations can be positive or negative (see Surge pressure). Hydraulic transients caused by normal pump and valve operation require the pipe system to withstand the resultant positive and negative pressures unless surge protection is provided.

* NSF International, 789 North Dixboro Road, Ann Arbor, MI 48105. †American National Standards Institute, 25 West 43rd Street, Fourth Floor, New York, NY 10036. ‡ Plastics Pipe Institute, 1825 Connecticut Avenue NW, Suite 630, Washington, DC 20005.

Note: For further information, see AWWA Manual M23, PVC Pipe—Design and Installation (3rd edition, forthcoming).

5. Hydrostatic design basis (HDB): The categorized long-term strength in the circumferential or hoop direction as established from long-term pressure tests in accordance with ASTM D2837. This standard requires the use of PVC compounds that qualify for an HDB rating of 4,000 psi (27.58 MPa) and finished pipe that qualifies for an HDB rating of 7,100 psi (49.0 MPa).
6. Hydrostatic design stress (HDS): The maximum allowable working hoop stress in the pipe wall when the pipe is subjected to sustained long-term hydrostatic pressure. The HDS in this standard is established by multiplying the HDB by the DF of 0.5.
7. Inspector: The authorized representative of the purchaser who is entrusted with the inspection of products and production records. The inspector also observes the production operations and quality-control tests to ensure products comply with the requirements of this standard and the purchaser.
8. Lot: Pipe manufactured during a production run.
9. Manufacturer: The party that manufactures, fabricates, or produces materials or products.
10. Molecularly oriented polyvinyl chloride (PVCO) pressure pipe: PVCO pipe is PVC pressure pipe that attains a relatively high circumferential strength by reorienting the molecules. To create PVCO pipe, conventionally extruded PVC pipe is expanded circumferentially (for example, 4-in. diameter starting stock pipe is conventionally extruded; it is then heated and expanded to 8-in. diameter) using pressure and temperature. The expansion reorients the PVC molecular structure in the hoop direction, thereby increasing the material strength in the hoop direction. Depending on the expansion process used, some longitudinal stretching is also possible.
11. Occasional (emergency or transient) surge pressure (P OS ): Surge pressures caused by emergency operations, usually the result of a malfunction (such as power failure, sudden valve closure, or system component failure).
12. Polyvinyl chloride (PVC) plastic: PVC resin, the basic building block of PVC pipe, is a polymer derived from saltwater, air, and natural gas or petroleum. PVC resin is combined with heat stabilizers, lubricants, and other ingredients to make PVC compounds that can be extruded into pipe or molded into fittings.

13. Pressure class (PC): The design capacity to resist working pressure up to 73.4°F (23°C) sustained operating temperature. The methods for determining pressure class are stated in Sec. 4.5.

14. Production run: The length of time a particular piece of extrusion equipment is producing a certain size of pipe.

15. Purchaser: The person, company, or organization that purchases any materials or work to be performed.

16. Reclaimed water: Wastewater that becomes suitable for beneficial use as a result of treatment.

17. Recurring (cyclic) surge pressure (P
RS
): Surge pressures that occur frequently and are inherent to the design and operation of the system (such as normal pump startup or shutdown and normal valve opening or closure). Recurring surge pressure may occur up to millions of times in a piping system’s lifetime

18. Safety factor (SF): The number by which the HDB is divided to calculate the HDS from which the PC is determined. Safety factor is the ratio of the stress capacity of the pipe or joining sleeves to the allowable stress. In this standard, the SF is 2.0. Also, the pipe minimum burst pressure divided by the SF equals the allowable occasional surge pressure.*

Note: The SF is the inverse of the design factor (DF) that appeared in the previous edition of this standard.

19. Starting stock: The conventionally extruded PVC pipe of uniform wall thickness that will be expanded to a larger diameter to orient the molecular structure.

20. Supplier: The party that supplies materials or services. A supplier may or may not be the manufacturer.

21. Surge pressure: The maximum hydraulic transient pressure increase (sometimes called water hammer) in excess of the operating pressure that is anticipated in the system as the result of sudden changes in velocity of the water column. For purposes of product selection and design, this document considers the following two types of surges:

a. Recurring (cyclic) surge pressure (P
RS
)

b. Occasional (emergency or transient) surge pressure (P
OS
)

Note: Occasional transients caused by emergency pump and valve operations are usually severe. The system should be designed to withstand positive and negative pressures caused by these emergency operations. Water column separation

may occur if the negative pressure is reduced to the vapor pressure of the liquid. Rejoining of the separated water column typically results in a large pressure rise, which will possibly damage the pipe system. Whenever possible, water column separation should be avoided.

22. Sustained operating temperature: The continuous long-term temperature of the pipe wall during service. A short-term rise in service temperature above 73°F (23°C) (for example, for a few weeks during summer) does not require use of temperature coefficients, FT , for pipeline design.
23. Wall-thickness-ratio (WTR): The ratio of the wall thickness of the finished PVCO pipe to the wall thickness of the starting stock.
24. Wastewater: A combination of the liquid and water-carried waste from residences, commercial buildings, industrial plants, and institutions, together with any groundwater, surface water, and stormwater that may be present.
25. Working pressure (WP): The maximum anticipated, sustained operating pressure applied to the pipe exclusive of transient pressures.

SECTION 4: REQUIREMENTS

Sec. 4.1 Permeation

The selection of materials is critical for water pipe in locations where there is likelihood the pipe will be exposed to significant concentrations of pollutants composed of low-molecular-weight petroleum products or organic solvents or their vapors. Documented research has shown that pipe materials (such as polyethylene, polybutylene, polyvinyl chloride, and asbestos cement) and elastomers (such as those used in jointing gaskets and packing glands) may be subject to permeation by lower-molecular-weight organic solvents or petroleum products. If a water pipe must pass through such a contaminated area or an area subject to contamination, consult with the manufacturer regarding permeation of pipe walls, jointing materials, and so forth before selecting materials for use in that area.

Sec. 4.2 Materials

4.2.1 Materials. Materials shall comply with the requirements of the Safe Drinking Water Act and other federal regulations for potable water, wastewater, and reclaimed water systems as applicable.
4.2.2 Pipe. PVC starting stock pipe shall be made from virgin PVC resin that has been compounded to provide physical and chemical properties that equal

or exceed cell class 12454, as defined in ASTM D1784, and shall qualify for a minimum HDB of 4,000 psi (27.58 MPa) at 73.4°F (23°C) in accordance with the requirements of PPI TR-3. Finished PVCO pipe shall have an HDB of 7,100 psi (49.0 MPa) as determined by testing in accordance with test method ASTM D1598, with data points in accordance with Table 5 and with data evaluation in accordance with ASTM D2837.

4.2.3 Rework materials. Clean rework materials derived from a manufacturer’s own pipe production may be used by the same manufacturer for similar purposes provided that (1) the cell classification of the rework material is identical to that of the material to which it will be added; (2) the rework material complies with applicable requirements of Sec. 4.2 of this standard; and (3) the finished products comply with the requirements of this standard.
4.2.4 Certification for potable water service. PVC compounds and products shall be tested for chemical extractants and certified as suitable for potable water service by an accredited testing agency acceptable to the purchaser. The basis of certification shall be the requirements specified in NSF/ANSI 61.
4.2.5 Gaskets and lubricants. Gaskets and lubricants intended for use with PVCO pipe shall be made from materials that are compatible with the pipe and with each other when used together. For potable applications, gaskets and lubricants shall not adversely affect the potable quality of the water that is to be transported.* For nonpotable applications, consideration must be given to constituents that might have an adverse effect on gaskets.
4.2.5.1 Elastomeric gaskets. One gasket shall be furnished with each bell end of every pipe. Elastomeric gaskets shall meet the requirements of ASTM F477 for high-head (50 ft [15 m] of head or higher) applications.

Sec. 4.3 Pipe Requirements

4.3.1 General. Except where specifically noted, all requirements shall apply to finished PVCO pipe.
4.3.2 Quality of work. When manufactured, pipe shall be homogeneous throughout; free from voids, cracks, inclusions, and other defects; and as uniform as commercially practical in color, density, and other physical properties. Pipe surfaces shall be free from nicks and significant scratches.† The joining surfaces of

* Foreword, Sec. I.C.

† For C909 pipe only, scratches that extend 10 percent or more into the pipe wall shall be considered significant.

pipe spigots and of integral-bell and sleeve-reinforced bell sockets shall be free of imperfections that might cause leakage at joints.

4.3.3 Dimensions.

4.3.3.1 Pipe barrel. The dimensions and tolerances of the pipe barrel shall conform with the applicable requirements listed in Table 1 when measured as specified in ASTM D2122.
4.3.3.2 Elastomeric-gasket bell ends. The dimensions of the integral bell ends shall meet one of the following requirements when measured according to ASTM D2122.

a. The bell wall thickness at any point shall conform to the ratio of the pipe’s outside diameter (OD) to its minimum wall thickness (t) except in the annular gasket ring groove and bell entry lip portions where the wall shall be at least the minimum thickness of the pipe barrel (Table 1).
b. Designs not meeting the requirements of Sec. 4.3.3.2(a) shall be tested to verify that the joint assemblies qualify for an HDB category of 7,100 psi (49.0 MPa) when tested in accordance with ASTM D2837 as modified in ASTM D3139.

4.3.3.3 Standard lengths. Pipe shall be provided in standard laying lengths of 20 ft ±1 in. (6.1 m ±25 mm), unless otherwise agreed on at the time of purchase.

4.3.4 Physical properties.

4.3.4.1 Accelerated regression. The pipe shall demonstrate a minimum HDB projection, at the 100,000-hour intercept, of 6,810 psi (47.0 MPa). (See Table 1 of ASTM D2837 for hydrostatic design basis categories.)
4.3.4.2 Sustained pressure. The pipe shall not fail, balloon, burst, or weep, as defined in ASTM D1598, at the applicable sustained pressure listed in Table 2 when six specimens are tested for 1,000 hours as specified in ASTM D2241. Either free-end or restrained-end closures that are free of leaks at maximum pressure shall be used.
4.3.4.3 Burst pressure. The quick-burst strength of pipe, including any integral bell end, shall meet the applicable minimum pressure requirements listed in Table 2 when tested in accordance with the specimen and sample sizes, conditioning, and procedural requirements of ASTM D1599. At least three of the five test specimens shall have a portion of the required markings located at least one pipe diameter away from an end closure. For bell-end pipe, the bell shall be included as a part of at least two test specimens. The ability to attain hydrostatic pressure equal to or greater than the values in Table 2 shall indicate passing this test requirement. The

Table 1 Dimensions and pressure classes for PVCO* pressure pipe with ductile-iron-pipeequivalent ODs
Nominal Size in. Pressure Class† OD—in. (mm) Wall Thickness—in. (mm)
psi (kPa) Average Tolerance ± Minimum Tolerance +
4 165 (1,140) 4.800 (121.92) 0.009 (0.23) 0.109 (2.77) 0.013 (0.33)
4 235 (1,620) 4.800 (121.92) 0.009 (0.23) 0.154 (3.91) 0.018 (0.47)
4 305 (2,100) 4.800 (121.92) 0.009 (0.23) 0.198 (5.02) 0.024 (0.60)
6 165 (1,140) 6.900 (175.26) 0.011 (0.28) 0.157 (3.98) 0.019 (0.48)
6 235 (1,620) 6.900 (175.26) 0.011 (0.28) 0.221 (5.62) 0.027 (0.67)
6 305 (2,100) 6.900 (175.26) 0.011 (0.28) 0.284 (7.22) 0.034 (0.87)
8 165 (1,140) 9.050 (229.87) 0.015 (0.38) 0.206 (5.22) 0.025 (0.63)
8 235 (1,620) 9.050 (229.87) 0.015 (0.38) 0.290 (7.36) 0.035 (0.88)
8 305 (2,100) 9.050 (229.87) 0.015 (0.38) 0.373 (9.47) 0.045 (1.14)
10 165 (1,140) 11.100 (281.94) 0.015 (0.38) 0.252 (6.40) 0.030 (0.77)
10 235 (1,620) 11.100 (281.94) 0.015 (0.38) 0.356 (9.03) 0.043 (1.08)
10 305 (2,100) 11.100 (281.94) 0.015 (0.38) 0.457 (11.61) 0.055 (1.39)
12 165 (1,140) 13.200 (335.28) 0.015 (0.38) 0.300 (7.61) 0.036 (0.91)
12 235 (1,620) 13.200 (335.28) 0.015 (0.38) 0.423 (10.74) 0.051 (1.29)
12 305 (2,100) 13.200 (335.28) 0.015 (0.38) 0.544 (13.81) 0.065 (1.66)
14 165 (1,140) 15.300 (388.62) 0.015 (0.38) 0.347 (8.83) 0.042 (1.06)
14 235 (1,620) 15.300 (388.62) 0.015 (0.38) 0.490 (12.45) 0.059 (1.49)
14 305 (2,100) 15.300 (388.62) 0.015 (0.38) 0.630 (16.01) 0.076 (1.92)
16 165 (1,140) 17.400 (441.96) 0.020 (0.51) 0.395 (10.04) 0.047 (1.20)
16 235 (1,620) 17.400 (441.96) 0.020 (0.51) 0.557 (14.16) 0.067 (1.70)
16 305 (2,100) 17.400 (441.96) 0.020 (0.51) 0.717 (18.20) 0.086 (2.18)
18 165 (1,140) 19.500 (495.30) 0.020 (0.51) 0.443 (11.25) 0.053 (1.35)
18 235 (1,620) 19.500 (495.30) 0.020 (0.51) 0.625 (15.87) 0.075 (1.90)
18 305 (2,100) 19.500 (495.30) 0.020 (0.51) 0.803 (20.40) 0.096 (2.45)
20 165 (1,140) 21.600 (548.64) 0.025 (0.64) 0.491 (12.46) 0.059 (1.50)
20 235 (1,620) 21.600 (548.64) 0.025 (0.64) 0.692 (17.58) 0.083 (2.11)
20 305 (2,100) 21.600 (548.64) 0.025 (0.64) 0.890 (22.60) 0.107 (2.71)
24 165 (1,140) 25.800 (655.32) 0.030 (0.76) 0.586 (14.88) 0.070 (1.79)
24 235 (1,620) 25.800 (655.32) 0.030 (0.76) 0.827 (21.00) 0.099 (2.52)
24 305 (2,100) 25.800 (655.32) 0.030 (0.76) 1.063 (26.99) 0.128 (3.24)
30 165 (1,140) 32.000 (813.82) 0.040 (1.02) 0.735 (18.66) 0.088 (2.24)
30 235 (1,620) 32.000 (813.82) 0.040 (1.02) 1.025 (26.04) 0.126 (3.20)
30 305 (2,100) 32.000 (813.82) 0.040 (1.02) 1.334 (33.89) 0.160 (4.07)
*Hydrostatic design stress = 3,550 psi (24,500 kPa).
†Pressure class at 73.4°F (23°C).
Table 2 Pressure-test requirements
Pressure Class* Sustained-Test Pressure Burst-Test Pressure Hydrostatic-Test Pressure
psi (kPa) psi (kPa) psi (kPa) psi (kPa)
165 (1,140) 350 (2,420) 535 (3,690) 330 (2,280)
235 (1,620) 500 (3,450) 755 (5,210) 470 (3,240)
305 (2,100) 650 (4,490) 985 (6,800) 610 (4,210)
*Pressure class at 73.4°F (23°C).
Table 3 Temperature coefficients, F T
Pipe Temperature Pressure Rating Reduction Coefficient
°F (°C)
80 (27) 0.88
90 (32) 0.75
100 (38) 0.62
110 (43) 0.50
120 (49) 0.40
130 (54) 0.30

time of testing of each specimen shall be not less than 60 seconds. Times greater than 60 seconds may be needed to bring the larger-sized specimens to the burst pressure.

Note: Times greater than 60 seconds are needed because of increased expansion for larger sizes. In addition, the test is more difficult to pass using longer pressuring times.

4.3.4.4 Hydrostatic integrity. The pipe, including any integral bell end, shall not fail, balloon, burst, or weep when subjected to an internal pressure equal to two times its designated pressure class, as listed in Table 2, for a minimum dwell time of 5 seconds. Integral bells shall be tested with the pipe. When the test temperature (the temperature of the pipe wall) is higher than 73.4°F (23°C), the test pressure may be reduced by applying the appropriate temperature coefficient from Table 3. Test temperature shall be estimated by measuring the temperature on the pipe’s outside surface within 20 minutes after hydrotesting is completed.

4.3.4.5 Flattening. The flattening test procedure and failure criteria shall conform to ASTM D2412. The specified distance between the plates is 40 percent of the OD of the pipe. The rate of flattening shall be uniform and such that the compression is completed within 2 to 5 minutes.

4.3.4.6 Extrusion quality. Unexpanded pipe shall not fail when tested by the acetone-immersion method as specified in ASTM D2152.
4.3.4.7 Apparent hoop tensile test. Specimens shall be cleanly cut from the pipe and tested in accordance with ASTM D2290. The apparent hoop tensile strength at yield shall not be less than 160 percent of the tensile strength of the pipe material specified in Sec. 4.2.2 (e.g., cell class 12454). A substitute for this test is the burst pressure test in accordance with Sec. 4.3.4.3.

Sec. 4.4 Joint Requirements

Bell-end pipe designed for making PVCO joints using elastomeric gaskets to effect a pressure seal shall be tested as assembled joints and shall meet the laboratory performance requirements specified in ASTM D3139. (These are qualifying test requirements to determine proper design and performance of specimen joints.) The pressure increase from 2½ times rated to minimum short-term rupture requirement shall occur within a minimum of 60 seconds. A time of greater than 60 seconds is permitted for larger sizes.

Note: Times greater than 60 seconds may be needed to bring the larger-sized specimens to burst pressure. In addition, this test is more difficult to pass using greater pressuring times.

Sec. 4.5 Pressure-Class Designations

4.5.1 Pressure class. This standard classifies pipe in accordance with its pressure class (PC). The following expression, commonly known as the ISO equation, is used to calculate the PC:

PC = (2 / (DR -1)) ×(HDB / SF) (1)

Where:

P C = Pressure class, psi

D R = Dimension ratio

H D B = Hydrostatic design basis, 7,100 psi

rl SF = & Safetyfactoristheratioofthestresscapacityofthepipetothe & allowablestress; inthisstandardthesafetyfactor(SF) is2.0

4.5.1.1 Temperature. For pipe that meets the requirements of this standard, the PC denotes the maximum working pressure (WP) rating for water at 73.4°F (23°C). When higher sustained operating temperatures are anticipated, the pipe’s PC shall be reduced by the appropriate temperature-compensating multiplier (F
T
) found in Table 3.

4.5.1.2 Maximum pressure. In all cases the maximum anticipated WP cannot exceed the pipe’s pressure class times the temperature coefficient.

WP < PC timesFT (2)

4.5.1.3 Pressure-class ratings. Pressure-class ratings for pipe described in this standard are given in Table 1. The PC values listed are the maximum WP ratings of pipe made and classified in accordance with this standard. They assume the pipe is not subject to surge pressures or hydraulic transients above the WP in excess of those defined in Sec. 4.5.1.4, and the pipe’s sustained operating temperature is at or below 73.4°F (23°C).
4.5.1.4 Surge pressure allowance. Previous editions of this standard have included a built-in generic surge allowance or occasional surge pressure capacity equivalent to a 2-ft/sec (0.6-m/sec) velocity change. This edition of the standard has removed this surge allowance in favor of expanded coverage of the two types of surge pressure: occasional and recurring. These changes are intended to allow users to analyze surge conditions specific to their projects.
4.5.1.4.1 Occasional surge pressure (POS) is a typical design parameter for most municipal water systems. Mathematically, occasional surge pressure is a simple concept that is easily accommodated by use of short-term pressure ratings or© occasional surge pressure capacities found in Table 4.
4.5.1.4.2 Occasional surge pressure capacity (WP + POS) , or short-term pressure rating, is the sum of the maximum anticipated WP and maximum anticipated occasional surge pressure. Occasional surge pressure capacity cannot exceed the short-term pressure rating, which is 1.60 times the pipe’s pressure class times FT . The defined occasional surge pressure capacities and corresponding allowable velocity changes are provided in Table 4.

WP + POS < 1.60PC timesFT (3)

4.5.1.4.3 Recurring surge pressure (PRS) develops high-frequency, highamplitude surge conditions that are not typically a design issue for municipal water systems but may need to be considered. Pipe selection or design to accommodate recurring surge pressure is a function of three variables (average stress, stress amplitude, and number of cycles to failure) and thus does not lend itself to tabular treatment. The body of the standard contains a limited discussion. The manufacturer should be consulted for additional guidance.

4.5.1.4.4 Recurring surge pressure capacity (WP + PRS) . Recurring surge pressure capacity is the sum of the maximum anticipated working pressure and the

Table 4 Allowable maximum occasional surge pressure* capacity and allowable sudden changes in water velocity for pipe operating at 73°F (23°C) at working pressures expressed as percent of nominal PC
Pressure Class† Pressure Surge for 1 ft/sec (0.3 m/sec) Sudden Delta V Occasional Surge Pressure Capacity Corresponding Sudden Delta V With WP = % of PC
psi (kPa) psi (kPa) psi (kPa) 100% ft/sec 80% ft/sec 60% ft/sec 40% ft/sec
165 (1,140) 11.8 (82) 264 (1,820) 8.34 11.2 14.0 16.8
235 (1,620) 14.1 (97) 376 (2,600) 10.00 13.4 16.7 20.1
305 (2,100) 16.0 (110) 488 (3,360) 11.50 15.3 19.1 22.9
*See Section 3 for definition of occasional surge pressure.
A pipe may sometimes be subjected to net negative internal pressure because of the individual or combined effect of internal negative transients and external forces (such as water table). When this situation exists, refer to the supplier for information on the hydraulic collapse resistance of the pipeline.
Tabular surge-pressure values are for a velocity change of 1.0 ft/sec. For actual surge pressure, multiply the appropriate tabular value by the actual velocity change.
†The surge pressure tolerances in this table apply only to pipe and not to system components, which may have lesser tolerances. The design should consider a transient analysis to determine possible system reactions and their potential effect on system components.

maximum anticipated surge pressure. Recurring surge pressure capacity cannot exceed the pipe’s pressure class times the temperature coefficient.

WP + PRS < PC timesFT (4)

SECTION 5: VERIFICATION

Sec. 5.1 Quality-Control and Qualification Test Requirements

The manufacturer shall take adequate measures in the production of PVCO pipe products that comply with the requirements of this standard. The pipe shall be tested at 73.4 ±3.6° ~F (23 ±2° C
) , unless otherwise specified, in accordance with the requirements of Sec. 4.3 and 4.4 at intervals as required in this standard.

5.1.1 Pipe dimensions. The dimensions of pipe produced from each extrusion outlet and each expansion unit, and the bell or sleeve-reinforced bell of pipe with such ends, shall be measured in accordance with Sec. 4.3.3 at the beginning of production of each specific material and each size. Thereafter, one specimen from each extrusion outlet and expansion unit shall be measured each hour.

Table 5 Time to failure for individual data points (accelerated regression test)
Time in Hours (hours)
10.0 to 99.99 hours
100 to 999.9 hours
1,000 to 1,999.9 hours
More than 2,000 hours
10.0 to 2,000+ hours (random point)
10.0 to 2,000+ hours (random point)

5.1.2 Accelerated regression test. This test shall be completed on a representative diameter at initial startup in accordance with Sec. 4.3.4.1. A representative diameter is one that has an expansion ratio (ER), a wall-thickness ratio (WTR), and a compound that is the same as the other diameters manufactured. Thereafter, it shall be completed on a representative diameter whenever there is a change in the ER or the WTR, or whenever a change is made to the compound that is outside the allowable limits of the Plastics Pipe Institute PVC compound range formula (see PPI TR-3). Testing shall be in accordance with procedures in ASTM D1598. A sample consisting of a minimum of six specimens shall be tested at pressures© selected to yield data points shown in Table 5. Additional points may be added if necessary to improve projection or lower confidence level,* or both. No points shall be excluded unless an obvious defect is detected in the failure area of the test sample. Results shall be characterized using the least-squares extrapolation described in ASTM D2837. (These tests are for qualification of the extrusion and expansion process and not for quality control of the product.)

5.1.3 Sustained pressure. At the beginning of production and semiannually thereafter, specimens of 4-in. (100-mm) or 6-in. (150-mm) pipe and of 8-in. (200-mm) or larger-size pipe that are made from each PVCO pressure pipe commercial compound (i.e., material) shall be tested in accordance with Sec. 4.3.4.2. (These tests are for qualification of the compound and the extrusion and orienting process and not for quality control of the product.)

5.1.4 Pipe burst strength. The quick-burst strength of pipe produced from each expansion unit shall be tested in accordance with Sec. 4.3.4.3 at the begin-

* Refer to ASTM D2837 and PPI TR-3.

ning of production of each specific material and each size. Thereafter, one specimen from each expansion unit shall be tested every 24 hours or, for nominal pipe sizes greater than 12 in., at least one specimen shall be tested per production run (lot) or every 100 lengths of pipe produced from each expansion unit, whichever is more frequent. As an alternative to the burst strength test, the apparent hoop tensile strength test may be conducted in accordance with Sec. 4.3.4.7.

5.1.5 Flattening capability. The flattening capability of pipe shall be tested in accordance with Sec. 4.3.4.5 at the beginning of production run from each expansion unit for each specific material and each size. The test shall be run immediately following any change from establishing running conditions that could affect orientation quality. Thereafter, one specimen from each extrusion outlet shall be tested every 8 hours for nominal pipe sizes less than 14 in. Changes in color pigment that meet the requirements of PPI TR-2 or TR-3 do not constitute a separate compound. The normal variations inherent in handling technique, processing equipment, and measuring precision do not constitute a change in the compound.
5.1.6 Extrusion quality. Unexpanded pipe produced from each extrusion outlet shall be tested in accordance with Sec. 4.3.4.6 at the beginning of a production run of each specific material and each size. The test shall also be run immediately following any change from established running conditions that would affect extrusion quality.
5.1.7 Provision for test failure. When any PVCO product fails to meet a requirement specified in this standard or in a referenced standard, additional tests shall be performed to determine which products are acceptable of those produced since the last favorable test. Products that fail to meet any requirement shall be rejected.
5.1.8 Hydrostatic proof test for pipe. Each length of pipe shall be proof tested in accordance with Sec. 4.3.4.4.
5.1.9 Optional test frequency. The purchaser or supplier may allow the manufacturer to conduct hydrostatic proof tests for pipes at test frequencies other than required in Sec. 5.1.8. Each purchaser in the distribution chain shall be notified if this option is used.

Sec. 5.2 Quality-Control Records

The manufacturer shall maintain, for a period of not less than two years, a record of all quality-control tests and shall, if requested, submit the pertinent record to the purchaser.

Sec. 5.3 Plant Inspection

5.3.1 Plant access. The purchaser’s inspector shall have free access at reasonable times to those parts of a manufacturer’s plant that are necessary to ensure that products comply with all requirements.
5.3.2 Responsibility for compliance. Plant inspection by the purchaser or the omission of such inspections shall not relieve the manufacturer of the responsibility to provide materials complying with the applicable requirements of this standard.

SECTION 6: DELIVERY

Sec. 6.1 Marking

6.1.1 General. Pipe shall bear identification markings that will remain legible during normal handling, storage, and installation. The markings shall be applied in a manner that will not reduce the strength of any product described by this standard.
6.1.2 Pipe. Marking on the pipe shall include the following and shall be applied at intervals of not more than 5 ft (1.5 m):©

. Nominal size in inches and OD base [for example, 4 DI (ductile iron)].
2 . PVCO.
3. AWWA pressure class (for example, PC 165).
4. Test pressure for hydrotested pipe (for example, T330), or if not tested, “NOT HYDROSTATIC PROOF TESTED.”
5. AWWA designation number for this standard (ANSI/AWWA C909).
6. Manufacturer’s name or trademark and production run record or lot code, to include date of starting stock extrusion and the date the finished pipe is expanded.
7. Seal (mark) of the testing agency that verified the suitability of the pipe material for potable water service (Sec. 4.2.4).
8. The words “Do Not Use Solvent Cement.”

Sec. 6.2 Shipping and Delivery

6.2.1 Shipping. All pipe shall, unless otherwise required in the purchase documents, be prepared for standard commercial shipment.

6.2.2 Delivery. Pipe that does not comply with the applicable requirements of this standard or that is damaged when received shall be replaced by the manufacturer or supplier at the agreed point of delivery.

Sec. 6.3 Affidavit of Compliance

The manufacturer shall, if required in the purchase documents, provide an affidavit that all delivered materials comply with the requirements of this standard and of the purchaser.

Sec. 6.4 Notice of Nonconformance

Any pipe not conforming to the requirements of this standard shall be made satisfactory or replaced. The purchaser must provide a notice of nonconformance to the supplier that explains the reason for nonconformance.

This page intentionally blank.

APPENDIX A

Bibliography

This appendix is for information only and is not a part of ANSI/AWWA C909.

ANSI/AWWA C605—Underground Installation of Polyvinyl Chloride (PVC) and Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe and Fittings. ANSI/AWWA C900—Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 In. Through 12 In. (100 mm Through 300 mm), for Water Transmission and Distribution.

ANSI/AWWA C905—Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 In. Through 48 In. (350 mm Through 1,200 mm) for Water Transmission and Distribution. ANSI/AWWA C907—Injected-Molded Polyvinyl Chloride (PVC) Pressure Fittings, 4 In Through 12 In. (100 mm Through 300 mm), for Water, Wastewater, and Reclaimed Water.

文档天下