ASTM D1785-15 E2018 Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40

文档天下 国外标准评论3阅读模式

1 Scope*

1.1 This specification covers poly(vinyl chloride) (PVC) pipe made in Schedule 40, 80, and 120 sizes and pressure-rated for water (see Appendix X1). Included are criteria for classifying PVC plastic pipe materials and PVC plastic pipe, a-- system of nomenclature for PVC plastic pipe, and requirements,,,, and test methods for materials, workmanship, dimensions,`, sustained pressure, burst pressure, flattening, and extrusion,, quality. Methods of marking are also given., ,

1.2 The products covered by this specification are intended--, for use with the distribution of pressurized liquids only, which,, , are chemically compatible with the piping materials. Due to-- inherent hazards associated with testing components and systems with compressed air or other compressed gases some manufacturers do not allow pneumatic testing of their products. Consult with specific product/component manufacturers for their specific testing procedures prior to pneumatic testing.

NOTE 1—Pressurized (compressed) air or other compressed gases contain large amounts of stored energy which present serious saftey hazards should a system fail for any reason.

NOTE 2—This standard specifies dimensional, performance and test requirements for plumbing and fluid handling applications only. It does not include provisions for the use of these products for venting of combustion gases. UL 1738 is a standard that does include specific testing and marking requirements for flue gas venting products, including PVC.

1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.

1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

1.5 The following safety hazards caveat pertains only to the test methods portion, Section 8, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.A specific precautionary statement is given in Note 9.

NOTE 3—CPVC plastic pipes, Schedules 40 and 80, which were formerly included in this specification, are now covered by Specification F441/F441M.

NOTE 4—The sustained and burst pressure test requirements, and the pressure ratings in the Appendix X1, are calculated from stress values obtained from tests made on pipe 4 in. (100 mm) and smaller. However, tests conducted on pipe as large as 24-in. (600-mm) diameter have shown these stress values to be valid for larger diameter PVC pipe.

NOTE 5—PVC pipe made to this specification is often belled for use as line pipe. For details of the solvent cement bell, see Specification D2672 and for details of belled elastomeric joints, see Specifications D3139 and D3212.

1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

2 Referenced Documents

2.1 ASTM Standards:
2

D618 Practice for Conditioning Plastics for Testing D1598 Test Method for Time-to-Failure of Plastic Pipe Under Constant Internal Pressure

D1599 Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings

D1600 Terminology for Abbreviated Terms Relating to Plastics

1 This specification is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.25 on Vinyl Based Pipe.

Current edition approved Aug. 1, 2015. Published August 2015. Originally approved in 1960. Last previous edition approved in 2012 as D1785 – 12. DOI: 10.1520/D1785-15E01.

2 For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards volume information, refer to the standard’s Document Summary page on the ASTM website.

D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds

D2122 Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings

D2152 Test Method for Adequacy of Fusion of Extruded Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by Acetone Immersion

D2672 Specification for Joints for IPS PVC Pipe Using Solvent Cement

D2837 Test Method for Obtaining Hydrostatic Design Basis for Thermoplastic Pipe Materials or Pressure Design Basis for Thermoplastic Pipe Products

D3139 Specification for Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals

D3212 Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals

F412 Terminology Relating to Plastic Piping Systems

F441/F441M Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe, Schedules 40 and 80

2.2 Federal Standard:

Fed. Std. No. 123 Marking for Shipment (Civil Agencies)

2.3 Military Standard:

MIL-STD-129 Marking for Shipment and Storage
3

2.4 NSF/ANSI Standards:
4
,,,,,

Standard No. 14 for Plastic Piping System Components and``` Related Materials,,, Standard No. 61 for Drinking Water System Components—, Health Effects``-

2.5 UL Standard:
5
,, ,,

UL 1738 Standard for Venting Systems for Gas-Burning,,`- Appliances, Categories II, III, and IV

3 Terminology

3.1 Definitions:—Definitions are in accordance with Terminology F412 and abbreviations are in accordance with Terminology D1600, unless otherwise specified. The abbreviation for poly(vinyl chloride) plastic is PVC.

3.2 Definitions of Terms Specific to This Standard:

3.2.1 hydrostatic design stress—the estimated maximum tensile stress the material is capable of withstanding continuously with a high degree of certainty that failure of the pipe will not occur. This stress is circumferential when internal hydrostatic water pressure is applied.

3.2.2 pressure rating (PR)—the estimated maximum water pressure the pipe is capable of withstanding continuously with a high degree of certainty that failure of the pipe will not occur.

3.2.3 relation between dimensions, design stress, and pressure rating—the following expression, commonly known as

3 Available from Standardization Documents Order Desk, DODSSP, Bldg. 4, Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098, http://dodssp.daps.dla.mil.

4 Available from NSF International, P.O. Box 130140, 789 N. Dixboro Rd., Ann Arbor, MI 48113-0140, http://www.nsf.org.

the ISO equation,
6 is used in this specification to relate dimensions, hydrostatic design stress, and pressure rating:

2S / P = (D0 / t) -1

where:

5 Available from Underwriters Laboratories (UL), 2600 N.W. Lake Rd., Camas, WA 98607-8542, http://www.ul.com.

S = hydrostatic design stress, psi (or MPa),

P = pressure rating, psi (or MPa),

D0 = average outside diameter, in. (or mm), and

t = minimum wall thickness, in. (or mm).

3.2.4 standard thermoplastic pipe materials designation code—the pipe materials designation code shall consist of the abbreviation PVC for the type of plastic, followed by the ASTM type and grade in Arabic numerals and the design stress in units of 100 psi (0.7 MPa) with any decimal figures dropped. When the design stress code contains less than two figures, a cipher shall be used before the number. Thus a complete material code shall consist of three letters and four figures for PVC plastic pipe materials (see Section 5).

4 Classification

4.1 General—This specification covers PVC pipe made to and marked with one of six type/grade/design stress designations (see X1.2) in Schedule 40, 80, and 120 wall sizes.

4.2 Hydrostatic Design Stresses—This specification covers pipe made from PVC plastics as defined by four hydrostatic design stresses which have been developed on the basis of long-term tests (Appendix X1).

5 Materials and Manufacture

5.1 General—Poly(vinyl chloride) plastics used to make pipe meeting the requirements of this specification are categorized by means of two criteria, namely, (1) short-term strength tests and (2) long-term strength tests. NOTE 6—The PVC pipe intended for use in the transport of potable water should be evaluated and certified as safe for this purpose by a testing agency acceptable to the local health authority. The evaluation should be in accordance with requirements for chemical extraction, taste, and odors that are no less restrictive than those included in NSF/ANSI Standard No. 14. The seal or mark of the laboratory making the evaluation should be included on the pipe. See pipe marking requirement for reclaimed water systems.

5.2 Basic Materials—This specification covers pipe made from PVC plastics having certain physical and chemical properties as described in Specification D1784.

5.3 Compound—The PVC compounds used for this pipe shall equal or exceed the following classes described in Specification D1784; PVC 12454, or 14333.

5.4 Rework Material—The manufacturer shall use only his own clean rework pipe material and the pipe produced shall meet all the requirements of this specification.

6 Requirements

6.1 Dimensions and Tolerances:

6 ISO R161-1960, Pipes of Plastics Materials for the Transport of Fluids (Outside Diameters and Nominal Pressures) Part 1, Metric Series.

ASTM D1785-15ε1

6.1.1 Dimensions and tolerances shall be as shown in Table 1 and Table 2 when measured in accordance with Test Method D2122. The tolerances for out-of-roundness shall apply only to pipe prior to shipment.

6.2 Sustained Pressure—The pipe shall not fail, balloon, burst, or weep as defined in Test Method D1598, at the test pressures given in Tables 3-5 when tested in accordance with 8.4.

TABLE 1 Outside Diameters and Tolerances for PVC Plastic Pipe Schedules 40, 80, and 120, in. (mm)
Nominal Pipe Size Outside Diameter Tolerances
Average Maximum Out-of-Roundness diam Schedule 40 sizes 31⁄2 in. and over; Schedule 80 sizes 8 in. and over (maximum minus minimum eter) Schedule 40 sizes 3 in. and less; Schedule 80 sizes 6 in. and less; Schedule 120 sizes all
1⁄8 0.405 (10.29) ±0.004 (±0.10) . . . 0.016 (0.41)
1⁄4 0.540 (13.72) ±0.004 (±0.10) . . . 0.016 (0.41)
3⁄8 0.675 (17.14) ±0.004 (±0.10) . . . 0.016 (0.41)
1⁄2 0.840 (21.34) ±0.004 (±0.10) . . . 0.016 (0.41)
3⁄4 1.050 (26.67) ±0.004 (±0.10) . . . 0.020 (0.51)
1 1.315 (33.40) ±0.005 (±0.13) . . . 0.020 (0.51)
11⁄4 1.660 (42.16) ±0.005 (±0.13) . . . 0.024 (0.61)
11⁄2 1.900 (48.26) ±0.006 (±0.15) . . . 0.024 (0.61)
2 2.375 (60.32) ±0.006 (±0.15) . . . 0.024 (0.61)
21⁄2 2.875 (73.02) ±0.007 (±0.18) . . . 0.030 (0.76)
3 3.500 (88.90) ±0.008 (±0.20) . . . 0.030 (0.76)
31⁄2 4.000 (101.60) ±0.008 (±0.20) 0.100 (2.54) 0.030 (0.76)
4 4.500 (114.30) ±0.009 (±0.23) 0.100 (2.54) 0.030 (0.76)
5 5.563 (141.30) ±0.010 (±0.25) 0.100 (2.54) 0.060 (1.52)
6 6.625 (168.28) ±0.011 (±0.28) 0.100 (2.54) 0.070 (1.78)
8 8.625 (219.08) ±0.015 (±0.38) 0.150 (3.81) 0.090 (2.29)
10 10.750 (273.05) ±0.015 (±0.38) 0.150 (3.81) 0.100 (2.54)
12 12.750 (323.85) ±0.015 (±0.38) 0.150 (3.81) 0.120 (3.05)
14 14.000 (355.60 ±0.015 (±0.38) 0.200 (5.08) . . .
16 16.000 (406.40) ±0.019 (±0.48) 0.320 (8.13) . . .
18 18.000 (457.20) ±0.019 (±0.48) 0.360 (9.14) . . .
20 20.000 (508.00) ±0.023 (±0.58) 0.400 (10.2) . . .
24 24.000 (609.60) ±0.031 (±0.79) 0.480 (12.2) . . .
TABLE 2 Wall Thicknesses and Tolerances for PVC Plastic Pipe, Schedules 40, 80, and 120, A,B in. (mm)
Nominal Pipe Size Wall ThicknessA
Schedule 40 Schedule 80 Schedule 120
Minimum Tolerance Minimum Tolerance Minimum Tolerance
1/8 0.068 (1.73) +0.020 (+0.51) 0.095 (2.41) +0.020 (+0.51) ... ...
1/4 0.088 (2.24) +0.020 (+0.51) 0.119 (3.02) +0.020 (+0.51) ... ...
3/8 0.091 (2.31) +0.020 (+0.51) 0.126 (3.20) +0.020 (+0.51) ... ...
1/2 0.109 (2.77) +0.020 (+0.51) 0.147 (3.73) +0.020 (+0.51) 0.170 (4.32) +0.020 (+0.51)
3/4 0.113 (2.87) +0.020 (+0.51) 0.154 (3.91) +0.020 (+0.51) 0.170 (4.32) +0.020 (+0.51)
1 0.133 (3.38) +0.020 (+0.51) 0.179 (4.55) +0.021 (+0.53) 0.200 (5.08) +0.024 (+0.61)
11/4 0.140 (3.56) +0.020 (+0.51) 0.191 (4.85) +0.023 (+0.58) 0.215 (5.46) +0.026 (+0.66)
11/2 0.145 (3.68) +0.020 (+0.51) 0.200 (5.08) +0.024 (+0.61) 0.225 (5.72) +0.027 (+0.68)
2 0.154 (3.91) +0.020 (+0.51) 0.218 (5.54) +0.026 (+0.66) 0.250 (6.35) +0.030 (+0.76)
21/2 0.203 (5.16) +0.024 (+0.61) 0.276 (7.01) +0.033 (+0.84) 0.300 (7.62) +0.036 (+0.91)
3 0.216 (5.49) +0.026 (+0.66) 0.300 (7.62) +0.036 (+0.91) 0.350 (8.89) +0.042 (+1.07)
31/2 0.226 (5.74) +0.027 (+0.68) 0.318 (8.08) +0.038 (+0.96) 0.350 (8.89) +0.042 (+1.07)
4 0.237 (6.02) +0.028 (+0.71) 0.337 (8.56) +0.040 (+1.02) 0.437 (11.10) +0.052 (+1.32)
5 0.258 (6.55) +0.031 (+0.79) 0.375 (9.52) +0.045 (+1.14) 0.500 (12.70) +0.060 (+1.52)
6 0.280 (7.11) +0.034 (+0.86) 0.432 (10.97) +0.052 (+1.32) 0.562 (14.27) +0.067 (+1.70)
8 0.322 (8.18) +0.039 (+0.99) 0.500 (12.70) +0.060 (+1.52) 0.718 (18.24) +0.086 (+2.18)
10 0.365 (9.27) +0.044 (+1.12) 0.593 (15.06) +0.071 (+1.80) 0.843 (21.41) +0.101 (+2.56)
12 0.406 (10.31) +0.049 (+1.24) 0.687 (17.45) +0.082 (+2.08) 1.000 (25.40) +0.120 (+3.05)
14 0.437 (11.10) +0.053 (+1.35) 0.750 (19.05) +0.090 (+2.29) ... ...
16 0.500 (12.70) +0.060 (+1.52) 0.843 (21.41) +0.101 (+2.57) ... ...
18 0.562 (14.27) +0.067 (+1.70) 0.937 (23.80) +0.112 (+2.84) ... ...
20 0.593 (15.06) +0.071 (+1.80) 1.031 (26.19) +0.124 (+3.15) ... ...
24 0.687 (17.45) +0.082 (+2.08) 1.218 (30.94) +0.146 (+3.71) ... ...
A The minimum is the lowest wall thickness of the pipe at any cross section. The maximum permitted wall thickness, at any cross section, is the minimum wall thickness plus the stated tolerance. All tolerances are on the plus side of the minimum requirement.
B These dimensions conform to nominal IPS dimensions, with the exception that Schedule 120 wall thickness for pipe sizes 1⁄2 to 3 1 ⁄2 in. (12.5 to 87.5 mm), inclusive, are special PVC plastic pipe sizes.

6.2.1 Accelerated Regression Test—The accelerated regression test shall be used in place of both the sustained and burst pressure tests, at the option of the manufacturer. The test shall be conducted in accordance with 8.4.1. The pipe shall demonstrate a hydrostatic design basis projection at the 100 000-h intercept that meets the hydrostatic design basis category requirement (see Tables 3-5 and Test Method D2837) for the PVC material used in its manufacture. (Example: PVC 1120 pipe must have a minimum 100 000-h projection of 3830 psi (26.40 MPa) and 85 % lower confidence limit (LCL).

6.3 Burst Pressure—The minimum burst pressures for PVC plastic pipe shall be as given in Table 6, when determined in accordance with Test Method D1599. NOTE 7—Times greater than 60 s may be needed to bring large size specimens to burst pressure. The test is more difficult to pass using greater pressurizing times.

6.4 Flattening—There shall be no evidence of splitting, cracking, or breaking when the pipe is tested in accordance with 8.6.

6.5 Extrusion Quality—The pipe shall not flake or disintegrate when tested in accordance with Test Method D2152.

7 Workmanship, Finish, and Appearance

7.1 The pipe shall be homogeneous throughout and free of visible cracks, holes, foreign inclusions, or other defects. The pipe shall be as uniform as commercially practicable in color, opacity, density, and other physical properties. NOTE 8—Color and transparency or opacity should be specified in the--` contract or purchase order.,,,,

8 Test Methods

8.1 Conditioning—Condition the test specimens at 73.4 ± 3.6°F (23±2°C) and 50 6 10 % relative humidity for not less than 40 h prior to test in accordance with Procedure A of Practice D618, for those tests where conditioning is required.

8.2 Test Conditions—Conduct tests in the standard laboratory atmosphere of 73.4 6 3.6°F (23 6 2°C) and 50 6 10 % relative humidity, unless otherwise specified in the test methods or in this specification.

8.3 Sampling—The selection of the sample or samples of pipe shall be as agreed upon by the purchaser and seller. In case of no prior agreement, any sample selected by the testing laboratory shall be deemed adequate.

8.3.1 Test Specimens—Not less than 50 % of the test specimens required for any pressure test shall have at least a part of the marking in their central sections. The central section is that portion of pipe which is at least one pipe diameter away from an end closure.

8.4 Sustained Pressure Test—Select the test specimens at random. Test individually with water at the internal pressures given in Tables 3-5, six specimens of pipe, each specimen at least ten times the nominal diameter in length, but not less than 10 in. (250 mm) or more than 3 ft (1 m) between end closures and bearing the permanent marking on the pipe. Maintain the specimens at the pressure indicated for a period of 1000 h. Hold the pressure as closely as possible, but within 610 psi (±70 kPa) . Condition the specimens at the test temperature of 73.4°F (23°C) to within 3.6°F (±2°C) . Test in accordance with Test Method D1598, except maintain the pressure at the values

TABLE 3 Sustained Pressure Test Conditions for Water at 73°F (23°C) for PVC Plastic Pipe, Schedule 40 TABLE 4 Sustained Pressure Test Conditions for Water at 73°F (23°C) for PVC Plastic Pipe, Schedule 80
Nominal Pipe Size Pressure Required for TestA
PVC1120PVC1220PVC2120 PVC2116 PVC2112 PVC2110
in. psi
1/8 1690 1360 1130 930
1/4 1640 1310 1090 900
3/8 1310 1050 870 720
1/2 1250 1000 840 690
3/4 1010 810 680 550
1 950 760 630 520
11/4 770 620 520 420
11/2 690 560 460 380
2 580 470 390 320
21/2 640 510 430 350
3 590 440 370 300
31/2 500 400 340 280
4 470 370 310 260
5 410 330 270 220
6 370 300 250 200
8 330 260 220 180
10 300 240 200 160
12 280 220 180 150
14 270 220 180 150
16 270 220 180 150
18 270 220 180 150
20 260 210 170 140
24 250 200 170 140
in. MPa
1/8 11.65 9.38 7.79 6.41
1/4 11.31 9.03 7.52 6.21
3/8 9.03 7.24 6.00 4.96
1/2 8.62 6.89 5.79 4.76
3/4 6.96 5.58 4.69 3.79
1 6.55 5.24 4.34 3.59
11/4 5.31 4.27 3.59 2.90
11/2 4.76 3.86 3.17 2.62
2 4.00 3.24 2.69 2.21
21/2 4.41 3.52 2.96 2.41
3 4.07 3.03 2.55 2.07
31/2 3.45 2.76 2.34 1.93
4 3.24 2.55 2.14 1.79
5 2.83 2.28 1.86 1.52
6 2.55 2.07 1.72 1.38
8 2.28 1.79 1.52 1.24
10 2.07 1.65 1.38 1.10
12 1.93 1.52 1.24 1.03
14 1.89 1.54 1.26 1.05
16 1.89 1.54 1.26 1.05
18 1.89 1.54 1.26 1.05
20 1.82 1.47 1.19 0.98
24 1.75 1.40 1.19 0.98
psi MPa psi MPa
PVC1120 4200 29.0 PVC1120 4200 29.0
PVC1220 4200 29.0 PVC1220 4200 29.0
PVC2120 4200 29.0 PVC2120 4200 29.0
PVC2116 3360 23.2 PVC2116 3360 23.2
PVC2112 2800 19.3 PVC2112 2800 19.3
PVC2110 2300 15.9 PVC2110 2300 15.9
A The fiber stresses used to derive these test pressures are as follows:

given in Tables 3-5 for 1000 h. Failure of two of the six specimens tested shall constitute failure in the test. Failure of one of the six specimens tested in retest shall constitute failure in the test. Evidence of failure of the pipe shall be as defined in Test Method D1598.

8.4.1 Accelerated Regression Test—Test in accordance with procedures in Test Method D1598, using either free end or

Nominal Pipe Size Pressure Required for TestA
PVC1120PVC1220PVC2120 PVC2116 PVC2112 PVC2110
in. psi
1/8 2570 2060 1720 1410
1/4 2370 1900 1580 1300
3/8 1930 1540 1290 1060
1/2 1780 1430 1190 980
3/4 1440 1160 960 790
1 1320 1060 880 720
11/4 1090 870 730 600
11/2 990 790 660 540
2 850 680 570 460
21/2 890 710 590 490
3 790 630 520 430
31/2 730 580 480 400
4 680 540 450 370
5 610 490 400 330
6 590 470 390 320
8 520 410 340 280
10 490 390 330 270
12 480 380 320 260
14 470 380 320 260
16 470 370 310 260
18 460 370 310 250
20 460 370 300 250
24 450 360 300 250
in. MPa
1/8 17.72 14.21 11.86 9.72
1/4 16.34 13.10 10.90 8.96
3/8 13.31 10.62 8.89 7.31
1/2 12.27 9.86 8.20 6.76
3/4 9.93 8.00 6.62 5.45
1 9.10 7.31 6.07 4.96
11/4 7.52 6.00 5.03 4.14
11/2 6.83 4.96 4.55 3.72
2 5.86 4.69 3.93 3.17
21/2 6.14 4.90 4.07 3.38
3 5.45 4.34 3.59 2.96
31/2 5.03 4.00 3.31 2.76
4 4.69 3.72 3.10 2.55
5 4.21 3.38 2.76 2.28
6 4.07 3.24 2.69 2.21
8 3.59 2.83 2.34 1.93
10 3.38 2.69 2.28 1.86
12 3.31 2.62 2.21 1.79
14 3.29 2.66 2.24 1.82
16 3.29 2.59 2.17 1.82
18 3.22 2.59 2.17 1.75
20 3.22 2.59 2.10 1.75
24 3.15 2.52 2.10 1.75
A The fiber stresses used to derive these test pressures are as follows:

restrained end fittings. A minimum of six samples shall be tested. Test three specimens at a single pressure that will result in failures at or below 0.10 h. Test an additional three specimens at a single pressure that will result in failures at about 200 h. Generating additional data points to improve the LTHS or LCL, or both, is acceptable. No points shall be excluded unless an obvious defect is detected in the failure area

TABLE 5 Sustained Pressure Test Conditions for Water at 73°F (23°C) for PVC Plastic Pipe, Schedule 120
Nominal Pipe Size Pressure Required for TestA
PVC1120PVC1220PVC2120 PVC2116 PVC2112 PVC2110
in. psi
1/2 2130 1710 1420 1170
3/4 1620 1300 1080 890
1 1510 1200 1000 830
11/4 1250 1000 830 680
11/2 1130 900 750 620
2 990 790 660 540
21/2 980 780 650 540
3 930 750 620 510
31/2 810 640 540 440
4 900 720 600 490
5 830 660 550 450
6 780 620 520 430
8 760 610 510 420
10 770 620 510 420
12 710 570 480 390
in. MPa
1/2 14.69 11.79 9.79 8.07
3/4 11.17 8.96 7.45 6.14
1 10.41 8.27 6.89 5.72
11/4 8.62 6.89 5.72 4.69
11/2 7.79 6.21 5.17 4.27
2 6.83 5.45 4.55 3.72
21/2 6.76 5.38 4.48 3.72
3 6.41 5.17 4.27 3.52
31/2 5.58 4.41 3.72 3.03
4 6.21 4.96 4.14 3.38
5 5.72 4.55 3.79 3.10
6 5.38 4.27 3.59 2.96
8 5.24 4.21 3.52 2.90
10 5.31 4.27 3.52 2.90
12 4.90 3.93 3.31 2.69
A The fiber stresses used to derive these test pressures are as follows:
psi MPa
PVC1120 4200 29.0
PVC1220 4200 29.0
PVC2120 4200 29.0
PVC2116 3360 23.2
PVC2112 2800 19.3
PVC2110 2300 15.9

of the test sample, or there was a malfunction of the equipment. Characterize the data using the least squares regression described in Test Method D2837.

8.5 Burst Pressure—Determine the minimum burst pressure with at least five specimens in accordance with Test Method D1599. The time of testing of each specimen shall be between 60 and 70 s.

8.6 Flattening—Flatten three specimens of the pipe each at least 2 in. (50 mm) long, between parallel plates in a suitable press until the distance between the plates is 40 % of the outside diameter of the pipe or the walls of the pipe touch, whichever occurs first. The rate of loading shall be uniform and such that the compression is completed within 2 to 5 min. On removal of the load examine the specimens for evidence of splitting, cracking, or breaking.

9 Retest and Rejection

9.1 If the results of any test(s) do not meet the requirements of this specification, the test(s) shall be conducted again only

by agreement between the purchaser and seller. Under such agreement, minimum requirements shall not be lowered, changed, or modified, nor shall specification limits be changed. If upon retest, failure occurs, the quantity of product represented by the test(s) does not meet the requirements of this specification.

10 Product Marking

10.1 Quality of Marking—The marking shall be applied to the pipe in such a manner that it remains legible (easily read) after installation and inspection.

10.2 Content of Marking:

10.2.1 Marking on the pipe shall include the following, spaced at intervals of not more than 5 ft (1.5 m):

10.2.1.1 Nominal pipe size (for example, 2 in. (50 mm)),

10.2.1.2 Type of plastic pipe material in accordance with the designation code prescribed in 3.2.4, for example, PVC1120,

TABLE 6 Burst Pressure Requirements for Water at 73°F (23°C) for PVC Plastic Pipe, Schedules 40, 80, and 120
Nominal Pipe Size Min Burst PressuresA
Schedule 40 Schedule 80 Schedule 120
PVC1120 PVC2112 PVC1120 PVC2112 PVC1120 PVC2112
PVC1220 PVC2116 PVC1220 PVC2116 PVC1220 PVC2116
PVC2120 PVC2110 PVC2120 PVC2110 PVC2120 PVC2110
in. psi
1/8 2580 2020 3920 3060 ... ...
1/4 2490 1950 3620 2830 ... ...
3/8 1990 1560 2940 2300 ... ...
1/2 1910 1490 2720 2120 3250 2540
3/4 1540 1210 2200 1720 2470 1930
1 1440 1130 2020 1580 2300 1790
11/4 1180 920 1660 1300 1900 1490
11/2 1060 830 1510 1180 1720 1340
2 890 690 1290 1010 1510 1180
21/2 970 760 1360 1060 1490 1170
3 840 660 1200 940 1420 1110
31/2 770 600 1110 860 1230 960
4 710 560 1040 810 1380 1080
5 620 390 930 720 1260 990
6 560 440 890 700 1190 930
8 500 390 790 620 1160 910
10 450 350 750 580 1170 920
12 420 330 730 570 1090 850
14 410 320 720 570 ... ...
16 410 320 710 560 ... ...
18 410 320 700 550 ... ...
20 390 310 700 540 ... ...
24 380 300 680 530 ... ...
in. MPa
1/8 17.79 13.93 27.03 21.10 ... ...
1/4 17.17 13.45 24.96 19.52 ... ...
3/8 13.72 10.76 20.27 15.86 ... ...
1/2 13.17 10.27 18.76 14.62 22.41 17.52
3/4 10.62 8.34 15.17 11.86 17.03 13.31
1 9.93 7.79 13.93 10.89 15.86 12.34
11/4 8.14 6.34 11.45 8.96 13.10 10.27
11/2 7.31 5.72 10.41 8.14 11.86 9.24
2 6.14 4.76 8.89 6.96 10.41 8.14
21/2 6.69 5.24 9.38 7.31 10.27 8.07
3 5.79 4.55 8.27 6.48 9.79 7.65
31/2 5.31 4.14 7.65 5.93 8.48 6.62
4 4.90 3.86 7.17 5.58 9.51 7.45
5 4.27 2.69 6.41 4.96 8.69 6.83
6 3.86 3.03 6.14 4.83 8.20 6.41
8 3.45 2.69 5.45 4.27 8.00 6.27
10 3.10 2.41 5.17 4.00 8.07 6.34
12 2.90 2.28 5.03 3.93 7.52 5.86
14 2.87 2.24 5.04 3.99 ... ...
16 2.87 2.24 4.97 3.92 ... ...
18 2.87 2.24 4.90 3.85 ... ...
20 2.73 2.17 4.90 3.78 ... ...
24 2.66 2.10 4.76 3.71 ... ...
A The fiber stresses used to derive these test pressures are as follows:
psi MPa
PVC1120 6400 44.1
PVC1220 6400 44.1
PVC2120 6400 44.1
PVC2116 5000 34.5
PVC2112 5000 34.5
PVC2110 5000 34.5

10.2.1.3 Schedule (40, 80, or 120, whichever is applicable)-- and the pressure rating in pounds per square inch (megapas-,,,, cals) for water at 73°F (23°C) shown as the number followed, by psi (for example, 200 psi (1.4 MPa)). When the indicated,, pressure rating is lower than that calculated in accordance with, `,

3.2.3 (see Appendix X1), this shall be indicated by placing a star after the pressure rating,

10.2.1.4 This designation, ASTM D1785, including the year of issue, with which the pipe complies,

10.2.1.5 Manufacturer’s name (or trademark),

ASTM D1785-15ε1

10.2.1.6 Production code with which the manufacturer can trace the year, month, day, shift, plant and extruder of manufacture for this product, and

10.2.1.7 Pipe intended for the transport of potable water shall also include the seal or mark of the laboratory making the evaluation for this purpose, spaced at intervals specified by the laboratory. NOTE 9—Manufacturers using the seal or mark of a laboratory must obtain prior authorization from the laboratory concerned.

NOTE 10—It is common practice to dual mark Schedule 40 piping for potable water and DWV usage in which compliance with each applicable standard is met.

11 Quality Assurance

11.1 When the product is marked with this designation, D1785, the manufacturer affirms that the product was manufactured, inspected, sampled, and tested in accordance with this specification and has been found to meet the requirements of this specification.

12 Keywords

12.1 pressure pipe; PVC pipe; Schedule 40 pipe; Schedule 80 pipe; Schedule 120 pipe

SUPPLEMENTARY REQUIREMENTS

This requirement applies whenever a regulatory authority or user calls for product to be used to convey or to be in contact with potable water.

S1. Potable Water Requirement—Products intended for contact with potable water shall be evaluated, tested, and certified for conformance with NSF/ANSI Standard No. 61 or the health effects portion of NSF/ANSI Standard No. 14 by an

acceptable certifying organization when required by the regulatory authority having jurisdiction.

This requirement applies only to pipe to be used in systems that have not established other provisions for identification.

S2.Pipe Marking Requirement for Reclaimed Water Systems—Color identification of pipe shall be by (1) use of purple (violet) PVC material or (2) by use of continuous purple

stripes printed lengthwise on opposite sides of the pipe. The pipe shall be marked RECLAIMED WATER at intervals of 5 ft. or less.

These requirements apply only to federal/military procurement, not domestic sales or transfers.

S1. Pipe for Reclaimed-Water System—Pipe used in these systems shall be purple (violet) in color and it shall be marked Reclaimed Water
.

S2. Responsibility for Inspection—Unless otherwise specified in the contract or purchase order, the producer is responsible for the performance of all inspection and test requirements specified herein. The producer may use his own or any other suitable facilities for the performance of the inspection and test requirements specified herein, unless the purchaser disapproves. The purchaser shall have the right to perform any of the inspections and tests set forth in this specification where such inspections are deemed necessary to ensure that material conforms to prescribed requirements. NOTE S2.1—In U.S. Federal contracts, the contractor is responsible for inspection.

S3. Packaging and Marking for U.S. Government Procurement:

S3.1 Packaging—Unless otherwise specified in the contract, the materials shall be packaged in accordance with the supplier’s standard practice in a manner ensuring arrival at destination in satisfactory condition and which will be acceptable to the carrier at lowest rates. Containers and packing shall comply with Uniform Freight Classification rules or National Motor Freight Classification rules.

S3.2 Marking—Marking for shipment shall be in accordance with Fed. Std. No. 123 for civil agencies and MIL-STD-129 for military agencies. NOTE S3.1—The inclusion of U.S. Government procurement requirements should not be construed as an indication that the U.S. Government uses or endorses the products described in this specification.

APPENDIX

(Nonmandatory Information)

X1. SOURCE OF HYDROSTATIC DESIGN STRESSES

X1.1 The hydrostatic design stresses recommended by the Plastics Pipe Institute are used to pressure rate PVC plastic pipe. These hydrostatic design stresses are 2000 psi (14 MPa), 1600 psi (11 MPa), 1250 psi (9 MPa), and 1000 psi (7 MPa) for water at 73°F (23°C). These hydrostatic design stresses apply only to pipe meeting all the requirements of this specification.

X1.2 Six PVC pipe materials are included based on the requirements of Specification D1784 and the PPI-recommended hydrostatic design stresses as follows:

X1.2.1 Type I, Grade 1 (12454-B), with a hydrostatic design stress of 2000 psi (14 MPa), designated as PVC1120.

X1.2.2 Type I, Grade 2 (12454-C), with a hydrostatic design stress of 2000 psi (14 MPa), designated as PVC1220.

X1.2.3 Type II, Grade 1 (14333-D), with a hydrostatic design stress of 2000 psi (14 MPa), designated as PVC2120.

X1.2.4 Type II, Grade 1 (14333-D), with a hydrostatic design stress of 1600 psi (11.2 MPa), designated as PVC2116.

X1.2.5 Type II, Grade 1 (14333-D), with a hydrostatic design stress of 1250 psi (8.7 MPa), designated as PVC2112.

X1.2.6 Type II, Grade 1 (14333-D), with a hydrostatic,,,, design stress of 1000 psi (7.0 MPa), designated as PVC2110., ``

X1.3 The standard method for obtaining hydrostatic basis, ``` for thermoplastic pipe materials is Test Method D2837. Addi-, , `

tional information regarding the test method and other criteria used in developing these hydrostatic design stresses may be obtained from the Plastics Pipe Institute, a division of The Society of the Plastics Industry, 355 Lexington Ave., New York, NY 10017. These hydrostatic design stresses may not be suitable for materials that show a wide departure from a straight-line plot of log stress versus log time to failure. All the data available to date on PVC pipe materials made in the United States exhibit a straight-line plot under these plotting conditions.

X1.4 The pipe is rated for use with water at 73°F (23°C) at the maximum internal pressures shown in Tables X1.1-X1.3. Lower pressure ratings than those calculated in accordance with 3.2.3 may be recommended, at the option of the pipe manufacturer, in which case the SDR shall be included in the marking. Experience of the industry indicates that PVC plastic pipe meeting the requirements of this specification gives satisfactory service under normal conditions for a long period at these pressure ratings. The sustained pressure requirements are related to these ratings through the slopes of the strengthtime plots of these materials in pipe form.

X1.5 The hydrostatic design stresses recommended by the Plastics Pipe Institute are based on tests made on pipe ranging in size from 1⁄2 to 2
1
⁄2 in. (12.5 to 63.5 mm).

TABLE X1.1 Water Pressure Ratings at 73°F (23°C) for Schedule 40 PVC Plastic Pipe
Nominal Pipe Size Pressure RatingsA
PVC1120BPVC1220PVC2120 PVC2116 PVC2112B PVC2110B
in. psi
1/8 810 650 500 400
1/4 780 620 490 390
3/8 620 500 390 310
1/2 600 480 370 300
3/4 480 390 300 240
1 450 360 280 220
11/4 370 290 230 180
11/2 330 260 210 170
2 280 220 170 140
21/2 300 240 190 150
3 260 210 160 130
31/2 240 190 150 120
4 220 180 140 110
5 190 160 120 100
6 180 140 110 90
8 160 120 100 80
10 140 110 90 70
12 130 110 80 70
14 130 100 80 60
16 130 100 80 60
18 130 100 80 60
20 120 100 80 60
24 120 90 70 60
in. MPa
1/8 5.58 4.48 3.45 2.76
1/4 5.38 4.27 3.38 2.69
3/8 4.27 3.45 2.69 2.14
1/2 4.14 3.31 2.55 2.07
3/4 3.31 2.69 2.07 1.65
1 3.10 2.48 1.93 1.52
11/4 2.55 2.04 1.59 1.24
11/2 2.28 1.79 1.45 1.17
2 1.93 1.52 1.17 0.97
21/2 2.07 1.65 1.31 1.03
3 1.79 1.45 1.10 0.90
31/2 1.65 1.31 1.03 0.83
4 1.52 1.24 0.97 0.76
5 1.31 1.10 0.83 0.69
6 1.24 0.97 0.76 0.62
8 1.10 0.83 0.69 0.55
10 0.97 0.76 0.62 0.48
12 0.90 0.76 0.55 0.48
14 0.91 0.70 0.56 0.42
16 0.91 0.70 0.56 0.42
18 0.91 0.70 0.56 0.42
20 0.84 0.70 0.56 0.42
24 0.84 0.63 0.49 0.42
B See Appendix X1 for code designation.
A These pressure ratings apply only to unthreaded pipe. The industry does not recommend threading PVC plastic pipe in Schedule 40 dimensions in nominal pipe sizes 6 in. (150 mm) and smaller.
TABLE X1.2 Water Pressure Ratings at 73°F (23°C) for Schedule 80 PVC Plastic Pipe
Nominal Pipe Size, in. psi
PVC1120, PVC1220, PVC2120 PVC2116 PVC2112 PVC2110
Unthreaded Threaded Unthreaded Threaded Unthreaded Threaded Unthreaded Threaded
1/8 1230 610 980 490 770 380 610 310
1/4 1130 570 900 450 710 350 570 280
3/8 920 460 730 370 570 290 460 230
1/2 850 420 680 340 530 260 420 210
3/4 690 340 550 280 430 210 340 170
1 630 320 500 250 390 200 320 160
11/4 520 260 420 210 320 160 260 130
11/2 470 240 380 190 290 150 240 120
2 400 200 320 160 250 130 200 100
21/2 420 210 340 170 260 130 210 110
3 370 190 300 150 230 120 190 90
31/2 350 170 280 140 220 110 170 90
4 320 160 260 130 200 100 160 80
5 290 140 230 120 180 90 140 70
6 280 140 220 110 170 90 140 70
8 250 120 200 100 150 80 120 60
10 230 120 190 90 150 70 120 60
12 230 110 180 90 140 70 110 60
14 220 ... 180 ... 140 ... 110 ...
16 220 ... 180 ... 140 ... 110 ...
18 220 ... 180 ... 140 ... 110 ...
20 220 ... 170 ... 140 ... 110 ...
24 210 ... 170 ... 130 ... 110 ...
MPa
1/8 8.48 4.21 6.76 3.38 5.31 2.62 4.21 2.14
1/4 7.79 3.93 6.21 3.10 4.90 2.41 3.93 1.93
3/8 6.34 3.17 5.03 2.55 3.93 2.00 3.17 1.59
1/2 5.86 2.90 4.69 2.34 3.65 1.79 2.90 1.45
3/4 4.76 2.34 3.79 1.93 2.96 1.45 2.34 1.17
1 4.34 2.21 3.45 1.72 2.69 1.38 2.21 1.10
11/4 3.59 1.79 2.90 1.45 2.21 1.10 1.79 0.90
11/2 3.24 1.65 2.62 1.31 2.0 1.03 1.65 0.83
2 2.76 1.38 2.21 1.10 1.72 0.90 1.38 0.69
21/2 2.90 1.45 2.34 1.17 1.79 0.90 1.45 0.76
3 2.55 1.31 2.07 1.03 1.59 0.83 1.31 0.62
31/2 2.41 1.17 1.93 0.97 1.52 0.76 1.17 0.62
4 2.21 1.10 1.79 0.90 1.38 0.69 1.10 0.55
5 2.00 0.97 1.59 0.83 1.24 0.62 0.97 0.48
6 1.93 0.97 1.52 0.76 1.17 0.62 0.97 0.48
8 1.72 0.83 1.38 0.69 1.03 0.55 0.83 0.41
10 1.59 0.83 1.31 0.62 1.03 0.48 0.83 0.41
12 1.59 0.76 1.24 0.62 0.97 0.48 0.76 0.41
14 1.54 ... 1.26 ... 0.98 ... 0.77 ...
16 1.54 ... 1.26 ... 0.98 ... 0.77 ...
18 1.54 ... 1.26 ... 0.98 ... 0.77 ...
20 1.54 ... 1.19 ... 0.98 ... 0.77 ...
24 1.47 ... 1.19 ... 0.91 ... 0.77 ...
TABLE X1.3 Water Pressure Ratings at 73°F (23°C) for Schedule 120 PVC Plastic Pipe
Nominal Pipe Size, PVC1120PV , PVC1220, C2120 PVC2116 psi PVC2112 PVC2110
in. Unthreaded Threaded Unthreaded Threaded Unthreaded Threaded Unthreaded Threaded
1⁄2 1010 510 810 410 630 320 510 250
3⁄4 770 390 620 310 480 240 390 190
1 720 360 570 290 450 220 360 180
11⁄4 600 300 480 240 370 190 300 150
11⁄2 540 270 430 210 340 170 270 130
2 470 240 380 190 290 150 240 120
21⁄2 470 230 370 190 290 150 230 120
3 440 220 360 180 280 140 220 110
31⁄2 380 190 310 150 240 120 190 100
4 430 220 340 170 270 130 220 110
5 400 200 320 160 250 120 200 100
6 370 190 300 150 230 120 190 90
8 380 180 290 140 230 110 180 90
10 370 180 290 140 230 110 180 90
12 340 170 270 140 210 110 170 80
1⁄2 6.96 3.52 5.58 2.83 MPa4.34 2.21 3.52 1.72
3⁄4 5.31 2.69 4.27 2.14 3.31 1.65 2.69 1.31
1 4.96 2.48 3.93 2.00 3.10 1.52 2.48 1.24
11⁄4 4.14 2.07 3.31 1.65 2.55 1.31 2.07 1.03
11⁄2 3.72 1.86 2.96 1.45 2.34 1.17 1.86 0.90
2 3.24 1.65 2.62 1.31 2.00 1.03 1.65 0.83
21⁄2 3.24 1.59 2.55 1.31 2.00 1.03 1.59 0.83
3 3.03 1.52 2.48 1.24 1.93 0.97 1.52 0.76
31⁄2 2.62 1.31 2.14 1.03 1.65 0.83 1.31 0.69
4 2.96 1.52 2.34 1.17 1.86 0.90 1.52 0.76
5 2.76 1.38 2.21 1.10 1.72 0.83 1.38 0.69
6 2.55 1.31 2.07 1.03 1.59 0.83 1.31 0.62
8 2.62 1.24 2.00 0.97 1.59 0.76 1.24 0.62
10 2.55 1.24 2.00 0.97 1.59 0.76 1.24 0.62
12 2.34 1.17 1.86 0.97 1.45 0.76 1.17 0.55

SUMMARY OF CHANGES

Committee F17 has identified the location of selected changes to this standard since the last issue (F1785–12) that may impact the use of this standard.

(1) Revised Note 2 to include reference to UL Standard 1738.

Added UL 1738 to Section 2, Referenced Documents.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should make your views known to the ASTM Committee on Standards, at the address shown below.

文档天下
  • 本文由 发表于 2026年11月22日 16:52:04
  • 转载请务必保留本文链接:https://www.998pdf.com/84037.html
匿名

发表评论

匿名网友 填写信息

:?: :razz: :sad: :evil: :!: :smile: :oops: :grin: :eek: :shock: :???: :cool: :lol: :mad: :twisted: :roll: :wink: :idea: :arrow: :neutral: :cry: :mrgreen: